SWITCH
POSITION
OFF
ON
0
2
ON
3
ON
4
ON
5
ON
4204
DIP SWITCH
FOR SETTING DEVICE ADDRESS
AND ENABLING/DISABLING TAMPER
COVER TAMPER (REED) SWITCH
4-PIN CONSOLE PLUG
EITHER OR BOTH
CAN BE USED
TB1
13 14 15 16
Figure 9-1: 4204 Relay Module
SWITCH
POSITION
OFF
ON
0
1
2
ON
—
3
ON
ON
4
ON
ON
5
ON
ON
DIP SWITCH
FOR SETTING DEVICE
ADDRESS AND
ENABLING/DISABLING
TAMPER
COVER TAMPER (REED) SWITCH
4-PIN CONSOLE PLUG
EITHER OR BOTH
CAN BE USED
TB1
13
14
15
16
YEL
DATA IN
FROM CONTROL
BLK
(–) GROUND
GRN
DATA OUT
TO CONTROL
RED
(+) 12V; SUPPLIES POWER TO MODULE
CIRCUITRY (INCLUDING NOTIFICATION
APPLIANCE RELAY COILS). CURRENT
DRAIN AT 12V IS: 25 mA + (80 mA PER
ACTIVE OUTPUT)
Figure 9-2: 4204CF Relay Module
4 2 0 4 A D D R E S S S E T T I N G S
("—" means "OFF")
1
2
3
4
5
6
7
8
—
ON
—
ON
—
ON
—
ON
ON
—
—
ON
ON
—
—
ON
ON
ON
ON
—
—
—
—
ON
ON
ON
ON
ON
ON
ON
ON
—
RELAY
4
TYPICAL
(SHOWN "OFF")
RELAY
3
RELAY
2
RELAY
1
YEL
DATA IN
FROM CONTROL
BLK
(–) GROUND
GRN
DATA OUT
TO CONTROL
RED
(+) 12V
4 2 0 4 C F A D D R E S S S E T T I N G S
("—" means "OFF")
2
3
4
5
6
7
8
ON
—
ON
—
ON
—
ON
—
—
ON
ON
—
—
ON
ON
ON
—
—
—
—
ON
ON
ON
ON
ON
ON
ON
—
–
NC
NC
+
POLARIZED
NC
NOTIFICATION
NC
APPLIANCE
–
+
NC
}
POWER FOR
NC
NOTIFICATION APPLIANCE A,
NOTIFICATION APPLIANCE B
8-28VDC OR VFW. UP TO 2.4A
TB2
DEPENDING ON BELL CURRENT
NOTIFICATION APPLIANCE AND
CONSOLE DATA OUTPUTS ARE
POWER LIMITED
Section 9 – Output Devices
9
10
11
12
13
14
15
—
ON
—
ON
—
ON
—
ON
—
—
ON
ON
—
—
ON
ON
ON
—
—
—
—
—
—
—
—
—
—
—
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
TB2
9
10
11
12
13
14
15
—
ON
—
ON
—
ON
—
ON
—
—
ON
ON
—
—
ON
ON
ON
—
—
—
—
—
—
—
—
—
—
—
- ALARM POLARITY
SHOWN
- EACH OUTPUT
NOTIFICATION
PROVIDES
APPLIANCE B
STYLE Y
2K EOLR
SUPERVISION
#610-7
- EACH OUTPUT
RATED 1.2A MAX
- USE
NOTIFICATION
APPLIANCES
COMPATIBLE
NOTIFICATION
WITH
APPLIANCE A
NOTIFICATION
2K EOLR
APPLIANCE
#610-7
POWER SUPPLY
VOLTAGE
RATING
9-3