ADEMCO VISTA-128B Installation And Setup Gude page 124

Partitioned security system with scheduling
Hide thumbs Also See for VISTA-128B:
Table of Contents

Advertisement

VISTA-128B Installation and Setup Guide
*90
SECONDARY SUBSCRIBER ACCT #
(partition-specific)
Enter the 3-or 4-digit number (depending on report format) for the secondary subscriber
account: 00-09; B-F (11-15). Each number requires a 2-digit entry to allow entry of
hexadecimal digits (B-F). If a 3-digit number is to be used, enter data only in the first 6
locations, leaving the last two unfilled. Default=15 15 15 15. Erase the field by entering
*90*. NOTE: This field must be programmed if a secondary phone number is used (field
*34). This account number can be the same as the primary account number.
1*07 CHECK OR TRBL DISPLAY
Enter 1 to display the letters TRBL instead of CHECK when a zone or system trouble
occurs.
Enter 0 to display CHECK.
1*10 FIRE DISPLAY LOCK
0 = scroll all alarms
1 = lock display of first fire alarm (press * to display other alarms)
1*17 LOBBY PARTITION
Enter the Common Lobby Partition (1-8).
Enter 0 if none.
1*18 AFFECTS LOBBY (partition-specific)
Enter 1 if this partition affects the common lobby. Will cause lobby to disarm when this
partition disarms.
Enter 0 if it does not.
1*19 ARMS LOBBY (partition-specific)
Enter 1 if arming this partition causes the system to attempt to arm the common lobby
partition automatically. Can only arm lobby if all other affecting partitions are armed.
To enable this field, field 1*18 must also be enabled (partition-specific).
Enter 0 if arming this partition will not attempt to arm the common lobby partition.
1*20 EXIT ERROR LOGIC ENABLE
Enter 1 to enable Exit Error Logic (entry/exit doors and interior zones will be bypassed
if left open).
Enter 0 if Exit Error Logic is not desired. Must be 0 for UL commercial burglary
installations.
1*21 EXIT DELAY RESET
Enter 1 to reset exit delay to 60 seconds after door is closed.
Enter 0 if exit delay not to be reset. Must be 0 for UL commercial burglary
installations.
1*22 CROSS ZONING PAIR ONE
Enter the first pair of zones, which must both be faulted within a five-minute period to
cause an alarm.
Enter 00,00 to disable. Must be 00,00 for UL burglary installations.
22-10
Enter 00-09; B-F (11-15)
|
|
|
[15
15
15
|
|
15]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
|