ADEMCO VISTA-128B Installation And Setup Gude page 125

Partitioned security system with scheduling
Hide thumbs Also See for VISTA-128B:
Table of Contents

Advertisement

1*23 CROSS ZONING PAIR TWO
Enter the second pair of zones, which must both be faulted within a five-minute period
to cause an alarm.
Enter 00,00 to disable. Must be 00,00 for UL burglary installations.
1*24 CROSS ZONING PAIR THREE
Enter the third pair of zones, which must both be faulted within a five-minute period to
cause an alarm.
Enter 00,00 to disable. Must be 00,00 for UL burglary installations.
1*25 CROSS ZONING PAIR FOUR
Enter the fourth pair of zones, which must both be faulted within a five-minute period
to cause an alarm.
Enter 00,00 to disable. Must be 00,00 for UL burglary installations.
1*26 PANIC BUTTON OR SPEEDKEY
For each lettered key A-C, enter 00 to assign that key's respective panic function, or
enter a speedkey macro number 01-32 to assign a particular macro to that key. For the
D key, enter 00 to use the D key to select a macro to execute when key is pressed, or
enter a macro number 01-32 to execute a particular macro with the D key.
Instead of the 32 macros, each key can be programmed for any of 3 other functions.
Choice 33 = fire sounder silence. The key, when pressed, will silence fire alarms.
Choice 34 = display next fire alarm. The key, when pressed, will display the next fire
alarm present in the system.
Choice 35 = display previous fire alarm. The key, when pressed, will display the
previous fire alarm present in the system.
Note: Choices 34 and 35 should be used in conjunction with field 1*10 Fire Display
Lock.
1*28 RF TX LOW BATTERY SOUND
Enter 0 if display and audible beep annunciation upon RF transmitter low battery
condition is desired only in disarmed state.
Enter 1 if audible beep and display is desired in both armed and disarmed states.
Must be 1 for UL.
1*29 RF TX LOW BATTERY REPORTING
Enter 1 if a Trouble message for RF transmitter low battery condition is to be sent to the
central station.
Enter 0 if no report for transmitter low battery is desired. Note that a Trouble message
will be sent for a transmitter supervision failure, independent of this selection.
Must be 1 for UL.
Section 22 – Data Field Descriptions
[00,00,00,00]
|
A
|
|
|
|
|
|
|
|
|
B
C
D
[0]
[0]
22-11