Section 20 – Zone Type Definitions
Type 10: Interior with Delay
Provides entry and exit delays (using the programmed entry/exit time), if tripped when the
panel is armed in the AWAY mode and exit delay only when armed in MAXIMUM mode.
Interior with Delay zones are automatically bypassed when the panel is armed in
the STAY or INSTANT mode. Delay begins whenever sensors in this zone are violated,
regardless of whether or not an entry/exit delay zone was tripped first.
Assign this zone type to a zone covering an area such as a foyer, lobby, or hallway through
which one must pass upon entry or exit (to and from the keypad).
Type 20: Arm-STAY
Causes the system to arm in the STAY mode when the zone is activated.
Type 21: Arm-AWAY
Causes the system to arm in the AWAY mode when the zone is activated.
Type 22: Disarm
Causes the system to disarm when the zone is activated.
Type 23: No Alarm Response
Used on a zone when an output relay action is desired, but with no accompanying alarm (e.g.,
for lobby door access).
Type 27: Access Point
Indicates that an input device (hardwired zone, wireless zone, keypad, access control relay,
etc.) is controlling an access point entry (e.g., a door). The access point entry relay can be
assigned to an access control relay (controlled by the VISTA-128B), ECP relay (4204), or to
the access control system independent of the VISTA-128B.
Type 28: Main Logic Board (MLB) Supervision
Used to supervise the MLB. If communication between the MLB and the Vista Gateway
Module (VGM) fails, a trouble condition is annunciated for the zone. Also, if the
communication fails, all access control system (ACS) input zones will also display a
"CHECK."
Type 29 Momentary on Exit
Used to cause an access point programmed for entry to revert to an exit point for 15 seconds.
After the 15 seconds it automatically reverts back to an entry point. This zone type should be
only used with VistaKey modules.
Note that these zone types are for use by 5800 Series devices only!
NOTE FOR PANIC KEYS: Keypad panic zones share the same zone response type for all 8
partitions, but panics may be individually enabled for each partition.
IMPORTANT! FAULT ANNUNCIATION
Polling loop and RF troubles (zones 988, 990 & 997) will report as trouble conditions only, and as
such, should be assigned zone type 05 if annunciation is desired. See Polling Loop Supervision
in the 2-Wire Polling Loop Expansion section and RF System Operation and Supervision in the
Wireless Expansion section for more information.