ADEMCO Vista-128FB Quick Start Manual

ADEMCO Vista-128FB Quick Start Manual

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for Vista-128FB:
Table of Contents

Advertisement

Quick Links

Previous Menu
9
,
6
7
$




)
%
9
,
6
7
$




)
%
&RPPHUFLDO)LUHDQG%XUJODU\
3DUWLWLRQHG6HFXULW\6\VWHP
ZLWK6FKHGXOLQJ
4XLFN6WDUW*XLGH
FIRE
FIRE
PULL
®
V128FB-PRV1 10/98

Advertisement

Table of Contents
loading

Summary of Contents for ADEMCO Vista-128FB

  • Page 1 Previous Menu &RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ 4XLFN6WDUW*XLGH FIRE FIRE PULL ® V128FB-PRV1 10/98...
  • Page 2 – –...
  • Page 3: Table Of Contents

    • To enter program mode, enter installer code + [8] + [0] + [0] + [0] • To set standard defaults, press *97 • To set communication defaults, press *94 + one of the following: *80=low speed; *81=Ademco Express; *82=Ademco High Speed; *83=Ademco's Contact ID •...
  • Page 4: When The System-Wide Fields Have Been Programmed, Program All Partition-Specific

    Recommended Programming Procedure The following is a step-by-step procedure recommended for programming your VISTA-128FB system. 1. Set the keypads (and other peripheral devices) to the appropriate addresses. 2. Set factory defaults by pressing *97. This will automatically enable keypad addresses 00-01, so be sure at least one keypad is set to one of these addresses 3.
  • Page 5 13. Exit Programming Mode. Exit programming mode by pressing either *98 or *99. Additional entries of *99 is required if the exit is being done from fields 1*00 and above. To prevent re-access to programming mode using the Installer's code, use *98. The only way to re-access programming mode is by depressing both the [*] and [#] keys at the same time within 30 seconds of power up.
  • Page 6: Program Field Categories

    Program Field Categories In the following pages, the programming fields have been arranged by category. Use this index to cross reference the numerical ordered fields on the programming form. Field Group Field Group Field Group System-Wide Communications 1*56 System-Wide System-Wide Communications 1*57 System-Wide...
  • Page 7 VISTA 128FB Programming Form Some fields are programmed for each partition (shown as shaded fields). If Programming a Multiple Partition System, see the PARTITION-SPECIFIC section for programming these fields. Standard default (*97) values are shown in brackets [ ], otherwise default = 0. | | | INSTALLER CODE IGNORE EXPANSION ZONE TAMPER...
  • Page 8 PAGER ID # FOR ALARMS 0=Ademco Low Speed; 1=Sescoa/Radionics SECONDARY FORMAT Enter up to 10 digits for the pager id # 0=Low Speed; 1=Contact ID; 2=Ademco High Speed; PAGER PHONE # FOR TROUBLES 3=Ademco Express LOW SPEED FORMAT (Sec.) 0=Ademco Low Speed; 1=Sescoa/Radionics Enter 0-9 for each digit.
  • Page 9 PAGER PHONE # FOR OPENS/CLOSES SEC. SUBS. ACCT # Enter 00-09; B-F (11-15) [15 15 15 15] 1*17 LOBBY PARTITION Enter the "common lobby" partition (1-8) Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause 1*18 AFFECTS LOBBY PAGER ID # FOR OPENS/CLOSES...
  • Page 10 1*42 1*74 CALL WAITING DEFEAT RELAY TIMEOUT XX MINUTES [000] Enter the relay timeout, 0-127 in multiples of 2 minutes, 1=Yes; 0=No desired for #80 Menu Mode time driven event relay 1*43 PERM. KEYPAD BACKLIGHT command numbers "04/09" and #93 Menu Mode Relay Programming output command "56".
  • Page 11 2*11 3*19 ALLOW DISARM OUTSIDE WINDOW ENABLE J2 HEADER PRINTER PORT IF ALARM OCCURS 0=pins 5&9 function as per field 3*20; 1=pins 5&9 act as printer RXD & DTR Used only if field 2*10 (partition-specific field) is set to "1". If this field is enabled ("1") the system can be disarmed 3*20 TRIGGER OUTPUTS SELECTION...
  • Page 12 To set standard defaults, press *97 • To set communication defaults, press *94 + one of the following: *80=low speed; *81=Ademco Express; *82=Ademco High Speed; *83=Ademco's Contact ID • To change to next page of program fields, press *94 •...
  • Page 13 Partition-Specific Fields (Duplicate this page for each partition in the installation.) To program these fields, 1. Press *91 to select a partition. 2. Enter a partition-specific field number (ex. *09). 3. Make the required entry. 4. Repeat steps 1-3 for each partition in the system. PARTITION #____ PROGRAM FIELDS 1st Page Fields ENABLE DIALER REPORTS[0]...
  • Page 14 To set communication defaults, press *94 + one of the following: *80=low speed; *81=Ademco Express; 2*10 ALLOW DISARMING ONLY DURING *82=Ademco High Speed; *83=Ademco's Contact ID ARMING/DISARMING WINDOWS • To change to next page of program fields, press *94 See system-wide field 2*11 if enabling field 2*10. This •...
  • Page 15: Programming With #93 Menu Mode

    Programming With #93 Menu Mode #93 Main Menu Options The following field should be programmed before beginning: 2*00: Number of Partitions. For commercial fire and UL Installations, verify that wireless and audio alarm verification features are disabled. After programming all system-related programming fields in the usual way, press #93 while still in Programming Mode to display the first choice of the menu-driven programming options, which are as follows: For programming the following: ZONE PROG?
  • Page 16: Zone Programming

    For defining the following device characteristics for addressable DEVICE PROG? devices, including keypads, RF receivers (5881), 4204/4204CF 0=No 1=Yes Output Relay Modules, 4285/4286 VIP Module and VGM: • Device address • Device type • Keypad options (includes partition assignment) • RF House ID For defining output relay functions.
  • Page 17 If a program tool is being used, enter 1. If not using a tool, PROGRAM TOOL? enter 0. When a 0 is entered, the system will advance to the 0 = NO, 1 = YES ENTER ZN NO. prompt. If 1 is entered, the system will prompt for the unit’s serial 000 INPUT S/N: L number.
  • Page 18 ↓ Zone Number Each zone must be assigned a zone type, which defines the way 010 ZONE RESPONSE in which the system responds to faults in that zone. Refer to Perimeter the Zone Type Definitions section for detailed definitions of Zone Type 03 entry shown each zone type.
  • Page 19 Enter the input device type as follows: 010 INPUT TYPE 00 = not used RF Xmitter 01 = hardwired Note that input types 4 & 5 are valid for certain 5800 03 = supervised RF transmitter (RF type) Series transmitters only (e.g., 04 = unsupervised RF transmitter (UR type) 5801, 5802, 5802CP &...
  • Page 20: Series Rf Transmitter Loop Designations

    5800 Series RF Transmitter Loop Designations LOOP LOOP LOOP (REED) (REED) LOOP 1 LOOP 1 (TERMINALS) (TERMINALS) LOOP ALTERNATE 5 8 1 6 5 8 1 6 M N (ALWAYS USE) POSITION ENROLL AS "RF" ENROLL AS "RF" FOR LOOP 2 5 8 0 2 / 5 8 0 2 C P ENROLL AS "BR"...
  • Page 21 This prompt is displayed if 1 (YES) is entered in response to 010 INPUT S/N the "LEARN S/N?" prompt. The serial number may be enrolled Axxx-xxxx by one of two methods: a) Enter the 7-digit serial number printed on the device using an alpha keypad.
  • Page 22 Sequential Mode Programming Usually, serial numbers are enrolled during Zone Programming. If not, use #93 Menu Mode to enroll serial numbers (for example, if all other programming was done via downloading). Use this mode only after all other zone information has been programmed, including transmitter loop numbers.
  • Page 23 Enter the first zone number to be enrolled (e.g., zone 010). ENTER ZN NO. Press [∗] to continue. (000 = QUIT) ↑ The system will, starting with this zone number, search for the Zone Number Entered first device which has all of the following attributes pre- programmed in Zone Programming: a) An input type of RF, UR, BR, or SL (if serial polling loop devices enabled) programmed...
  • Page 24 All report codes are entered using #93 Menu Mode Programming, either through Report Code Programming, or through the Zone Programming while entering other zone information. In the VISTA-128FB, reports are divided into six categories. These categories represent the main menu options found in the Report Code Programming.
  • Page 25 The programming sequence that follows assumes that you will be entering all reports for the system at one time. In actuality, you may skip from one main menu option to another by pressing 0 (N) at each main menu option. Main menu options are highlighted in bold text. To enter report codes, do the following: Enter Program Mode [Installer Code] + 8 0 0 0.
  • Page 26 Enter the first digit of the trouble restore code (single-digit TROUBLE RESTORE entry) and press [∗]. The second digit will be the ID (second) GRP 001-016 digit of the alarm report code for each zone (if programmed). Press [∗] to continue. Enter the first digit of the Bypass Report Code (double-digit BYPASS entry) and press [∗].
  • Page 27 System Group 2 Codes To enter System Group #2 codes, press 1 (Y). SYSTEM GROUP #2 ? 1 = YES 0 = NO Enter the first digit of the Arm-STAY report. Press [∗]. Enter STAY the second digit of the report. If the user number is desired as 1st 00 2nd 00 the second digit, enter 01 (not necessary for Contact ID or High...
  • Page 28 System Group 4 Codes To enter System Group #3 codes, press 1 (Y). SYSTEM GROUP #4 ? 1 = YES 0 = NO Enter the first digit of the Fire Test Start Report Code. Press WALK TEST START [∗]. Enter the second digit of the report code. 1st 00 2nd 00 Press [∗] to continue.
  • Page 29 PART DESCRIP? for creating 4-character partition names. EXIT EDIT MODE? Press 1 to exit back to #93 Menu Mode. 4. Refer to the sections that follow for procedures for adding alpha descriptors. Zone Descriptors 1. Select ZONE DESCRIPTOR mode. The keypad keys perform the following functions: Scrolls both alphabet and actual words in ascending alphabetical order.
  • Page 30 Store the descriptor. When all desired words have been entered, press 8 to store the description in memory. To review the zone descriptors, key [#] plus zone number (e.g., #001). To edit zone descriptors, key [∗] plus zone number (e.g., *001) Exit Zone Description Mode: enter 000.
  • Page 31 When using method 3b to enter alpha descriptors, each word will be found at the end of the group of words that begin with the same letter as it does. 6. Repeat steps 2 through 6 to create up to a maximum of 20 custom words (or word strings).
  • Page 32: Alpha Descriptor Vocabulary

    Alpha Descriptor Vocabulary (For Entering Alpha Descriptors. To select a word, press [#] followed by the word's 3-digit number.) NOTE: This vocabulary is not to be used for relay voice descriptors. See the RELAY VOICE DESCRIPTORS section when programming relay voice descriptors. 000 (Word Space) 107 HOUSE •...
  • Page 33 *Notes: This factory-provided vocabulary of words is subject to change. Bulleted words in bold face type are those that are also available for use by the 4285/4286 VIP Module. If using a VIP Module, and words other than these are selected for alpha descriptors, the Voice Module will not provide annunciation of those words.
  • Page 34 If device type 1 (alpha keypad) is entered, this prompt will SOUND OPTION appear. Keypads can be individually programmed to suppress arm/disarm beeps, entry/exit beeps and chime mode beeps. This helps prevent unwanted sounds from disturbing users in other areas of the premises. Enter a number 00-03 for the keypad sounding suppression options desired for the keypad as follows: 00 = no suppression.
  • Page 35 Long Range Radio If device type 6 is chosen, the 6139 Keypad will function similar to the 7720PLRR Programming Tool. See Figure 25-2 for the functions of the keys on the 6139. ARMED READY BS/ESC SPACE ENTER SHIFT SHIFT function indicated by turning on READY LED. Figure 25-2 6139 Key Functions for Programming 7820 Radio Each key has two possible functions: a normal function and a SHIFT function.
  • Page 36 The 6139 Keypad will display the following prompts, which are sent by the Long Range Radio transmitter to the control. Enter the device address of the radio. The default address is 3. DEVICE ADDRESS Enter the 4-digit customer account number, 0001-9999. This ID ID # number will appear in the messages generated by the radio.
  • Page 37 Relay Programming The system supports up to 32 relay outputs. Relays can be used to perform many different functions and actions. Each relay must be programmed to begin one of four types of ACTIONS at a designated START event, and end that ACTION at a designated STOP event. The options used to start and stop these devices are described below, followed by the actual screen prompts and available entries.
  • Page 38 If a specific "ZONE TYPE" is chosen, any zone of that response type going into alarm, trouble, or fault will cause the device to activate as selected in "ACTION.” If the same “ZONE TYPE” is also chosen for the STOP programming, any zone of that type that restores will de- activate the device.
  • Page 39 The keypad will display a summary STOP screen. A ZL ZT P Press [∗] to continue. 0 00 The Relay Action is the way in which the relay will respond 02 RELAY ACTION when activated by the "start" event. Enter the desired action NO RESPONSE for this relay as follows: 0=not used;...
  • Page 40 If the start zone type selected was 27 (access point), this prompt 02 START: ACS PT will be displayed. Enter the access point (00-31) which will (00-31) start the relay action. If the starting event will be limited to occurring on a specific 02 START PART partition, enter the partition number (1-8) in which the start event will occur.
  • Page 41 For relay modules (4204/4204CF), enter the actual relay ECP ADDRESS module's address (01-15) as set by its DIP switches. Up to 8 modules can be installed in a system. For 4204 Relay Outputs, enter the specific relay number on MODULE RELAY # that module (1-4).
  • Page 42 Press [∗] to scroll through all zones in that list. Enter 000 +[∗] XXX Assigned Zone to quit. 000=QUIT Press *99 to exit Program Mode. Relay Voice Descriptors If using the 4285/4286 VIP Module, voice descriptors can be programmed for each of the 32 relays used in the system.
  • Page 43: Relay Voice Descriptors And Custom Word Substitutes Vocabulary

    Relay Voice Descriptors and Custom Word Substitutes Vocabulary Word Index Word Index Word Index Word Index Word Index Air ....116 Daughter's ..208 Front ....087 No..... 165 Side ....153 Alarm ....255 Den....052 North....146 Six ..... 075 And....
  • Page 44 Custom Word Substitutes for VIP Module Annunciation A substitute word can be programmed for each of the 20 custom words used in your alpha zone descriptions. The VIP Module will announce this substitute word in place of the custom word that is displayed on the alpha keypad.
  • Page 45: System Layout Worksheets

    System Layout Worksheets As with any security system, you should first define the installation. This includes determining how many partitions will be used, how many zones per partition, and how many users per partition. You will also need to determine what peripheral devices will be needed, and basic system options such as exit/entry delays, etc. The control panel itself should be located in an area that will facilitate wire runs to all partitions, and will allow access to power and telephone circuits.
  • Page 46 SYSTEM DEFINITIONS BY PARTITION 9enter values or yes/no) Option Part. 1 Part. 2 Part. 3 Part. 4 Part. 5 Part. 6 Part. 7 Part. 8 Entry Delay #1 (15-225 seconds): Exit Delay #1 (15-225 seconds): Entry Delay #2 (15-225 seconds): Exit Delay #2 (15-225 seconds): Quick Arming Multiple Alarms per Arming...
  • Page 47 DEVICES (keypads, 4204, rf receivers, vip module, lrr, vgm) Device Home Sound Supv Keypad Device Home Sound Supv Keypad Address Type Part Global Address Type Part Global Type: Console Sounder Options: 0 = Device Not Used 00 = No Suppression 1 = Alpha Console 01 = Suppress Arm/Disarm and Entry/Exit Beeps 3 = RF Receiver...
  • Page 48 ACCESS CODES & USER DEFINITIONS FOR PARTITIONS 1-3 4-digit Access Partition 1 Partition 2 Partition 3 Security Group 2-Digit Global Auth. Open/ 2-Digit Global Auth. Open/ 2-Digit Global Auth. Open/ Code 0; 1-8 User # Arm? Level Close User # Arm? level Close...
  • Page 49 ZONE DEFINITIONS FOR ZONES 001-024 Parti- Input Serial # Zone Zone tion Type Device Bell/Relay Report Zone Information (part numbers) & Type (1-8) (1-8) Loop Activation Code Alpha Descriptor (3 words max.) — 49 —...
  • Page 50 ZONE DEFINTIONS FOR ZONES 025-048 Parti- Input Serial # Zone Zone tion Type Device Bell/Relay Report Zone Information (part numbers) & Type (1-8) (1-8) Loop Activation Code Alpha Descriptor (3 words max.) — 50 —...
  • Page 51 ZONE DEFINITIONS FOR ZONES 049-072 Parti- Input Serial # Zone Zone tion Type Device Bell/Relay Report Zone Information (part numbers) & Type (1-8) (1-8) Loop Activation Code Alpha Descriptor (3 words max.) — 51 —...
  • Page 52 ZONE DEFINTION FOR ZONES 073-096 Parti- Input Serial # Zone Zone tion Type Device Bell/Relay Report Zone Information (part numbers) & Type (1-8) (1-8) Loop Activation Code Alpha Descriptor (3 words max.) — 52 —...
  • Page 53 ZONE DEFINTION FOR ZONES 097-120 Parti- Input Serial # Zone Zone tion Type Device Bell/Relay Report Zone Information (part numbers) & Type (1-8) (1-8) Loop Activation Code Alpha Descriptor (3 words max.) — 53 —...
  • Page 54 ZONE DEFINTION FOR ZONES 121-128 Parti- Input Serial # Zone Zone tion Type Device Bell/Relay Report Zone Information (part numbers) & Type (1-8) (1-8) Loop Activation Code Alpha Descriptor (3 words max.) ZONE DEFINITIONS FOR KEYPAD PANIC ZONES 995, 996, & 999 Enter yes/no for each partition-field *22 Zone Zone...
  • Page 55 ZONE DEFINITIONS FOR RELAY SUPERVISORY ZONES 601-616 Zone Information (part numbers) Zone Information (part numbers) Zone Zone Report & Zone Zone Report & Type Code Alpha Descriptor (3 words max.) Type Code Alpha Descriptor (3 words max.) — 55 —...
  • Page 56 ZONE DEFINITIONS FOR SUPERVISORY OF ECP DEVICE ZONES 800-831 Zone Information (part numbers) Zone Information (part numbers) Zone Zone Report & Zone Zone Report & Type Code Alpha Descriptor (3 words max.) Type Code Alpha Descriptor (3 words max.) Zone Types: 00=zone not used 06=24 hour silent 16=Fire w/Verification...
  • Page 57: Output Relays Worksheets

    Output Relays Worksheets Applicable only if Relays (4204/4204CF) are to be used. Output Devices – Programmed in the #93 Menu Mode in the Relay Programming Section. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
  • Page 58 OUTPUT RELAYS WORKSHEET (cont’d) S T A R T S T O P either (EV) / (ZL) or (ZT) / (P) or both either (ZL) or (ZT)/(P) or both OUTPUT Dev Add Relay # DEV # (EV) (ZL) (ZT) (ZL) 1=4204 (ZT) for 4204...
  • Page 59 Choices for System Operation are: 20 = Arming-Stay 37 = 2 Times Bell Time-out* 52 = Kissoff 21=Arm Away 38 = Chime 54 = Fire Zone Reset 22 = Disarming 39 = Fire Alarm 55 = Disarm + 1 Minute 30 = On Second Off 40 = Bypassing 56 = XX Minutes...
  • Page 60: Scheduling Menu Prompts

    Scheduling Menu Prompts To program schedules, enter Scheduling program mode by pressing [Installer Code] + # + 80 to display the first choice of the menu driven programming functions. Press 0 (NO) or 1 (YES) in response to the displayed menu selection.
  • Page 61: Scheduling Worksheets

    Scheduling Worksheets Time Windows Definitions Worksheet. The system provides 20 time windows that are defined with start and stop times. They are programmed in the #80 Menu Mode. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
  • Page 62 Holiday Schedule Worksheet: The system provides up to 16 holidays that can be assigned for the system. Each holiday can be assigned to any combination of partitions. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
  • Page 63 Below is a list of the "Action" codes (desired actions) used when programming time driven events. Note that these codes are independent of the "relay codes" programmed during the #93 Menu Mode–Relay Programming mode. If using Time Driven Events to control relays, the following menu items must first be programmed using #93 Menu Mode - Relay Programming: Enter Relay No.
  • Page 64 Limitation of Access Worksheet The system provides up to 8 Access Schedules that can be programmed for the system. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
  • Page 65 Partition/Windows Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window Start Time HH:MM Stop Time HH:MM Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window Start Time HH:MM Stop Time HH:MM Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window Start Time...
  • Page 66 — 66 —...
  • Page 67: Summary Of Connections

    Ratings: 10 - 14VDC, 1.7A max. - Zones 1, 2, 8: 100 ohms max - 2mA max for smoke det. (up to 16 detectors 2k EOLR is Ademco model 610-7 See note 1, see instructions Polling Loop - Other zones: 300 ohms max of the type specified in the instructions for compatible devices.
  • Page 68 165 Eileen Way, Syosset, NY, 11791 Copyright © 1998 PITTWAY Corporation ¬9)%359l V128FB-PRV1 10/98...

Table of Contents