ZONE LIST (ZL) is a group of zones to which the "EVENT" applies in order to activate
a particular device. Note that there are a total of 15 zone lists that can be programmed;
when the selected EVENT (alarm, fault or trouble) occurs in any zone in the selected
"Start" ZONE LIST (01-15), activation of the selected device will START.
2) ZONE # A specific zone going into alarm, fault, trouble, or restore (Event programming)
can be used to start the relay action. Enter the 3-digit zone number (000-128).
3) ZONE TYPE/SYSTEM OPERATION (ZT). If all zones to be used to start the device
have the same response type, and there are no other zones of this type which are not to
activate this device, then "ZONE TYPE" may be used instead of using a "ZONE LIST"
and "EVENT" to activate the device.
If a System Operation, such as "DISARMING" or "ANY FIRE ALARM" is to activate the
device, the appropriate choice would also be entered under the "ZONE TYPE" option.
The "ZONE TYPE/SYSTEM OPERATION" option functions independently of the
"EVENT/ZONE LIST" combination.
If a specific "ZONE TYPE" is chosen, any zone of that response type going into alarm,
trouble, or fault will cause the device to activate as selected in "ACTION." If the same
"ZONE TYPE" is also chosen for the STOP programming, any zone of that type that
restores will de-activate the device.
If a "SYSTEM OPERATION" is chosen, that operation will cause the device to activate
as selected in "ACTION." The different choices for "ZONE TYPE" and "SYSTEM
OPERATION" are listed in "Programming Relays" later in this section, and on the
Programming Form.
4) PARTITION No. (P). The device's "Start" ZONE TYPE/SYSTEM OPERATION may be
limited to an occurrence on one partition (1-8), or any partition (0).
STOP (STP)
The "STOP" programming determines when and under what conditions the device will be
de-activated. The following options are available:
1). RESTORE ZONE LIST (ZL). If a "ZONE LIST" is used as the "Stop" event, the device
will de-activate when all the zones in that list restore from a previous fault, trouble, or
alarm condition. This will occur regardless of what is programmed to "START" the
device; therefore, a "RESTORE ZONE LIST" would normally only be used when a
"ZONE LIST" is used to start the device.
2). ZONE TYPE/SYSTEM OPERATION (ZT). Instead of using a "RESTORE ZONE
LIST," a specific zone (response) type or system operation action can be selected to de-
activate the device.
If a specific "ZONE TYPE" is chosen, any zone of that response type that restores from a
previous alarm, trouble, or fault condition will cause the device to de-activate.
If a "SYSTEM OPERATION" is chosen, that operation will cause the device to de-
activate. The different choices for "ZONE TYPE" and "SYSTEM OPERATION" are
listed in "Programming Relays" later in this section, and in the Programming Form.
3) PARTITION No. (P). The device's "Stop" Zone Type/System Operation may be limited
to an occurrence on one partition (1-8), or on any partition (0).
The "ZONE TYPE/SYSTEM OPERATION" option functions independently of the
"RESTORE/ZONE LIST" combination.
See the Programming Guide for a detailed explanation and the display prompts for
programming output devices.