Installing The 4204 Relay Module; Installing A 4285 Or 4286 Vip Module; Figure 2-10 4204 Connections To Control - ADEMCO VISTA-10ES Installation And Setup Manual

Table of Contents

Advertisement

Transmitter Input Types
All of the transmitters described have one or more
unique, factory-assigned input (loop) ID codes. Each of
the inputs requires its own programming zone (for
example: a 5804's four inputs require four programming
zones). Refer to SECTION 5: Zone Programming.
Transmitters can be enrolled as one of the following
types:
Type
Description
Sends periodic check-in signals, as
RF
well as fault, restore, and low
(Supervised RF)
battery signals. The transmitter
must remain within the receiver's
range.
UR
Sends all the signals that the "RF"
type does, but the control does not
(Unsupervised RF)
supervise the check-in signals. The
transmitter may therefore be carried
off-premises.
Sends only fault signals. It will not
BR
send a low battery signal until it is
(Unsupervised Button
activated. The transmitter may be
RF)
carried off-premises.
Using the Transmitter Sniffer Mode
The Transmitter Sniffer mode is a procedure that
verifies that all transmitters have been properly
programmed.
To verify programming, refer to SECTION 11: Testing
the System.

Installing a 4285 or 4286 VIP Module

1. Connect incoming phone line and handset wiring to
the main terminal block (via an RJ31X jack) as
shown in Figure 2-11 and in the Summary of
Connections diagram at the back of this manual.
Wire colors represent the colors of the cable to the
RJ31X jack.
±
2. Make
12VDC and data in/data out connections
from the control using the connector cable supplied
with the phone module, then insert the keyed
connector into the header on the phone module.
3. Connect Phone Module terminals as shown in
Figure 2-11. Use an RJ31X jack with a direct-
connect cord and make all connections as shown.
4. Caller ID Units: If a Caller ID unit is being used,
connect the unit directly to the "Handset" terminals
(17 and 18) on the control, as shown.
Section 2 – Installing the Control & Peripherals

Installing the 4204 Relay Module

1. Mount outside of the control panel's cabinet.
2. Connect to control's keypad terminals using the
connector harness supplied with the module. Use
standard 4-conductor twisted cable for long wiring
runs.
3. Set each of the module's four relays address to 12,
13, 14, and 15 (corresponding to relays 1 through 4
respectively).
4. Connect the desired field wiring to the unit's relay
contact terminals as indicated in Figure 2-10.
NOTES:
• Supervision: 4204 modules are supervised against
removal.
The module's device address is displayed as follows if
a module is disconnected from the control's terminals,
or if the module cover is removed and the tamper
jumper is installed:
Alpha keypads: DEV xx Wire Expansion Fault
Fixed-Word keypads: lxx
where "xx is the module's address.
4204
DIP SWITCH
FOR SETTING DEVICE ADDRESS
AND ENABLING/DISABLING TAMPER
COVER TAMPER (REED) SWITCH
4-PIN KEYPAD PLUG
EITHER OR BOTH
CAN BE USED
TB1
13 14 15 16
Figure 2-10. 4204 Connections to Control
NOTES:
• Use a 4285 or 4286 VIP (Phone) Module.
• Only one phone module can be used and it can
only be connected as shown in Figure 2-11.
• The phone lines must be in service for the phone
module to function, even when accessing the system
from an on-premises phone.
• If you are also using an Audio Alarm Verification
(AAV) unit, refer to Audio Alarm Verification (AAV)
paragraph later in this section for special wiring
connections.
VIP Modules are not Listed for UL installation
U L
use.
Phone Module Problems
RELAY
C
4
NC
TYPICAL
NO
(SHOWN "OFF")
C
RELAY
3
NC
NO
C
RELAY
2
NC
NC
NO
C
RELAY
1
NC
NO
YEL
TB2
DATA IN
FROM CONTROL
BLK
(–) GROUND
GRN
DATA OUT
TO CONTROL
RED
(+) 12V
4204_conn-V0
2-9

Advertisement

Table of Contents
loading

Table of Contents