Section 7. RELAY OUTPUT DEVICES

Relay Device Basics

4204 and 4229 Relay Modules
4204/4229 Setup

Supervision

COVER TAMPER (REED) SWITCH
Relays are programmable switches that can be used to perform many different
functions. They can be used to turn lights on and off, control sounders, or for
status indications. In this system, each relay must be programmed as to how
to act (ACTION), when to activate (START), and when to deactivate (STOP).
Each of these is described below, and in the programming procedure for 80
and 81 interactive modes that are provided at the end of this section.
The control supports the following relay modules:
4204 Relay Module (4 relays).
4229 Zone Expander/Relay Module (2 relays).
1. The 4204 and 4229 relays provide Form C (normally open and normally
closed) contacts.
2. A 4204 cannot be used if a 4219 or 4229 is already being used.
In
80 and
81 interactive modes, a series of keypad prompts will request
entries for programming of the Relay outputs used in the system. Refer also to
"OUTPUT RELAYS WORKSHEET FOR FIELDS
programming form provided in the separate Programming Guide manual.
The 4204 unit can be mounted either remotely or in the control panel. The
following steps should be taken to properly set up the 4204:
1. Connect the 4204 or 4229 module to the control's remote keypad
terminals (4–7), using the connector supplied with the module. Use
standard 4-conductor twisted cable for long wiring runs.
2. Set the 4204 or 4229's DIP switch for a device address of "1" (switch 2
"OFF" and switches 3, 4, and 5 "ON"). Switch 1 determines the unit's cover
tamper response ("ON" = disabled, "OFF" = enabled).
3. Connect the desired field wiring to the unit's relay contact terminals. See
Figures 10 and 11.
The 4204 and 4229 modules are supervised against removal. CHECK and
zone 09 will be displayed if a module is disconnected from the control's
keypad terminals (4, 5, 6, & 7).
4204
4204
DIP SWITCH
FOR SETTING DEVICE ADDRESS
AND ENABLING/DISABLING TAMPER
4-PIN CONSOLE PLUG
EITHER OR BOTH
CAN BE USED
13 14 15 16

Figure 10. 4204 Connections to Control

7 –1
RELAY 4
TYPICAL
(SHOWN "OFF")
TB1
YEL
DATA IN
FROM CONTROL
BLK
(–) GROUND
GRN
DATA OUT
TO CONTROL
RED
(+) 12V
80 AND 81" in the blank
C
NC
NO
C
RELAY
3
NC
NO
C
RELAY
2
NC
NO
C
RELAY
1
NC
NO
TB2