(N) Operation via communication and its settings

2.5
(N) Operation via communication and its
settings
Purpose
To start operation via
communication
To communicate via Ethernet
connector
Operation via communication
using the inverter-to-inverter link
function
2.5.1

Initial setting of operation via communication

Set the action at fault occurrence or at writing of parameters when the inverter is performing operation via
communication.
Pr.
Name
342
Communication
N001
EEPROM write selection
349
Communication reset
N010
selection

502
Stop mode selection at
N013
communication error

Operation frequency
779
during communication
N014
error

If in communication by the communication option, the "E.OP1" indication is displayed.

The parameter setting is valid when Pr.1431 Ethernet signal loss detection function selection = "3" or Pr.1432 Ethernet communication
check time interval  "9999" during Ethernet communication.

The parameter is used when the CC-Link IE Field Network Basic is selected. (Refer to
14
PARAMETER
Initial setting of operation
via communication
Initial setting of Ethernet
communication
CC-Link IE Field Network
Basic
Inverter-to-inverter link
function
Initial
Setting
value
range
0
0
1
0
0
1
0
1
0
2
3
4
0 to 590 Hz
9999
9999
Parameter to set
P.N001, P.N010,
P.N013, P.N014
P.N600 to P.N603,
P.N610 to P.N613,
P.N630 to P.N632,
P.N641 to P.N644,
P.N650, P.N651,
P.N660 to P.N666,
P.N670 to P.N675
P.N100, P.N103,
P.D400, P.H700
P.N681, P.N682
Description
Parameter values are written to the EEPROM and RAM by
communication.
Parameter values are written to the RAM only by communication.
Enables the error reset function in any operation mode.
Enables the error reset function only in the Network operation
mode.
Inverter operation when a
communication error
occurs
Output shutoff
"E.EHR" indication

ALM signal output
Output to decelerate and stop
the motor
"E.EHR" indication after stop

ALM signal output after stop
Output to decelerate and stop
the motor
"E.EHR" indication after stop

Operation continues at the
frequency set in Pr.779.
Operation continues at the
frequency set in Pr.779.
"CF" warning indication
Set the frequency for the operation when a communication error
occurs.
Operation continues at the same frequency before the
communication error.
page
51.)
Refer
to
page
Pr.342, Pr.349,
14
Pr.502, Pr.779
Pr.1424 to Pr.1429,
Pr.1431, Pr.1432,
19
Pr.1434 to Pr.1455
Pr.541, Pr.544,
51
Pr.804, Pr.810
Pr.1124, Pr.1125
72
Inverter operation after a
communication error is
cleared
Output stop status continues.
("E.EHR" indication
)

Output stop status continues.
("E.EHR" indication
)

Restart
Normal
Normal