Setting The Local/Remote Mode - Omron SYSDRIVE 3G3MV User Manual

Multi-function compact inverter sysdrive 3g3mv series
Hide thumbs Also See for SYSDRIVE 3G3MV:
Table of Contents

Advertisement

Basic Operation

5-4 Setting the Local/Remote Mode

The 3G3MV operates in local or remote mode. The following description
provides information on these modes and how to select them.
H Basic Concept
Operation mode
Local
Remote
H Local/Remote Selection Methods
·The following two selection methods are available to set the Inverter to local or remote
mode. However, it is not possible to switch between local and remote modes during
operation command input.
S Select the mode with the LO/RE Key of the Digital Operator.
S Set any one of multi-function inputs 1 through 7 (n050 through n056) to 17 to set the
Inverter to local mode with control input turned ON.
Note If the above setting is made, mode selection will be possible only with multi--func-
tion input, and not with the Digital Operator.
·The inverter always goes into remote mode when the power is turned ON. To operate
immediately after power--up, preset the RUN command and frequency reference set-
tings in remote mode.
5-10
Basic concept
The Inverter in a system
operates independently in
this mode so that the
Inverter can be checked
independently.
The Inverter in a system
operates according to the
control signal of the host
controller.
Description
Operation Command
Starts with the RUN Key of the Digital
Operator and stops with the
STOP/RESET Key.
Frequency Reference
Set with the Digital Operator or the FREQ
adjuster.
Set with frequency reference selection in
local mode in n007.
Operation Command
Selectable from four types and set in
n003.
Frequency Reference
Selectable from ten types and set in
n004.
Chapter 5

Hide quick links:

Advertisement

Table of Contents
loading