Advanced Operation
Stall Prevention Level
n093
during Acceleration
Setting
30 to 200 (%)
range
Set Values
·This function is used to stop accelerating the load if the output current exceeds the set
current value so that the Inverter will continue operating without stalling. The Inverter
accelerates the load while the output current is the same as or less than the set value.
·Set the parameter as percentage based on the rated Inverter current as 100%.
·The default setting does not need any changes in normal operation.
·Decrease the set value if the capacity of the motor is smaller than that of the Inverter or
the motor stalls with the default value.
The set value is normally 2 or 3 times higher than the rated current of the motor. Set this
current as percentage based on the rated inverter current as 100%.
Stall Prevention during Acceleration
Output
current
Output
frequency
n094
Stall Prevention Level
during Operation
Setting
30 to 200 (%)
range
Set Values
·This function will decrease the output frequency if the output current exceeds the set
current value by a minimum of approximately 100 ms so that the Inverter will continue
operating without stalling. The Inverter will increase the output frequency to return to
the set frequency reference level when the output current is less than the set value.
6-32
Register 015D
Hex
Unit of
1%
setting
The output frequency is controlled
so that the Inverter will not stall.
Register 015E
Hex
Unit of
1%
setting
Chapter 6
Changes during
No
operation
Set Values
170
n093 (stall prevention level
during acceleration)
Time
Time
Changes during
No
operation
Default setting
160