Omron SYSDRIVE 3G3MV User Manual page 197

Multi-function compact inverter sysdrive 3g3mv series
Hide thumbs Also See for SYSDRIVE 3G3MV:
Table of Contents

Advertisement

Communications
RS-422/485 Communica-
n151
tions Time-over Detection
Selection
Setting
0 to 4
range
Set Values
Value
0
Detects a time-over and fatal error and coasts to a stop (see note 1)
1
Detects a time-over and fatal error and decelerates to a stop in deceleration
time 1 (see note 1)
2
Detects a time-over and fatal error and decelerates to a stop in deceleration
time 2 (see note 1)
3
Detects a time-over and nonfatal error warning and continues operating. The
warning is canceled when the communications return to normal. (see note 2)
4
No time-over is detected.
Note 1. The fatal error is canceled with error reset input.
Note 2. The nonfatal error warning is canceled when the communications returns to
normal.
H Communications Frequency Reference/Display Unit Selection
(n152)
·Set this parameter to the unit of frequency reference and frequency-related values to
be set or monitored through communications.
·This unit is for communications use only and independent from the units of setting
made through the Digital Operator.
RS-422/485 Communica-
n152
tions Frequency Reference/
Display Unit Selection
Setting
0 to 3
range
Set Values
Value
0
0.1 Hz
1
0.01 Hz
2
Converted value based on 30,000 as max. frequency
3
0.1% (Max. frequency: 100%)
Register 0197
Hex
Unit of
1
setting
Description
Register 0198
Hex
Unit of
1
setting
Description
Chapter 7
Changes during
No
operation
Default setting
0
Changes during
No
operation
Default setting
0
7-3