Advanced Operation
Power Averaging Time
n143
Setting
1 to 200
range
Set Values
·Set n143 to the time required to calculate the average of power used in energy-saving
control.
Power averaging time (ms) = Set value in n143 x 24 (ms)
·Normally, the default setting does not need to be changed.
·The Inverter averages the power for the set time for energy-saving control.
·The value set in n143 is used for probe operation. The Inverter in probe operation
changes the voltage at intervals set in this parameter.
·Increase the set value if the power fluctuates frequently and the Inverter cannot per-
form stable energy control.
Energy-saving Voltage
n141
Lower Limit at 60-Hz Output
Setting
0 to 120 (%)
range
n142
Energy-saving Voltage
Upper Limit at 6-Hz Output
Setting
0 to 25 (%)
range
Set Values
·When the output frequency is constant for a certain period while the Inverter is in effec-
tive energy-saving control, the Inverter is set to the primary level of energy-saving con-
trol by n140. Parameter n141 and parameter n142 prevent the output voltage of the
Inverter from dropping excessively so that the motor will not stall or stop at that time.
·Set the lower limit of output voltage in percentage at each frequency based on the
rated motor voltage as 100%.
Register 018F
Hex
Unit of
1
setting
(24 ms)
Register 018D
Hex
Unit of
1%
setting
Register 018E
Hex
Unit of
1%
setting
Chapter 6
Changes during
No
operation
Default setting
1
Changes during
No
operation
Default setting
50
Changes during
No
operation
Default setting
12