Advanced Operation
Note If set to vector control mode, the default value will be 0.2.
Set Values
·This parameter is used for the response adjustment of the slip compensation function.
·The default setting does not need any changes in normal operation.
·Change the default setting in the following cases.
The motor vibrates:
The motor response is low:
n113
Slip Compensation During
Regeneration
Setting
0, 1
range
Set Values
Value
0
Slip compensation function disabled during regeneration
1
Slip compensation function enabled during regeneration
·Select whether the slip compensation function is enabled or not, even during regen-
eration (i.e.: when regeneration energy is returning during deceleration, etc.).
·This parameter is only enabled in vector control mode. (In V/f control mode, the slip
compensation function will be disabled during regeneration, regardless of the setting
for this parameter.)
6-40
Set the value to a larger value.
Set the value to a smaller value.
Register 0171
Hex
Unit of
1
setting
Description
Chapter 6
Changes during
No
operation
Default setting
0