Basic Operation
·Set the frequency of minimum analog input (0 V, 0 mA, or 4 mA) in n42 as percentage
based on the maximum frequency as 100%.
Example: In order to obtain 50% maximum frequency output with 0 V input, set the
value to 50%.
Frequency Reference Gain
n060
Setting
0% to 255%
range
(Max. frequency = 100%)
Frequency Reference Bias
n061
Setting
--99% to 99%
range
(Max. frequency = 100%)
D Filter Time Constant Settings (n062)
·A primary delay digital filter can be set for analog frequency references to be input.
·This setting is ideal if the analog input signal changes rapidly or the signal is subject to
noise interference.
·The larger the set value is, the slower the response speed will be.
Analog Frequency Reference
n062
Filter Time
Setting
0.00 to 2.00 (s)
range
H Multi-function Analog Input
An auxiliary analog input can be set for the Digital Operator's multi-function analog volt-
age/current input. Select from the following functions.
Multi-function Analog Input
n077
Terminal Function Selection
Setting
0 to 4
range
Multi-function Analog Input
n078
Terminal Selection
Setting
0, 1
range
Multi-function Analog Input
n079
Frequency Bias
Setting
0 to 50
range
Note Please also refer to page 2-20.
Register 013C
Changes during
Hex
operation
Unit of
1%
Default setting
setting
Register 013D
Changes during
Hex
operation
Unit of
1%
Default setting
setting
Register 013E
Changes during
Hex
operation
Unit of
0.01 s Default setting
setting
Register 014D
Changes during
Hex
operation
Unit of
1
Default setting
setting
Register 014E
Changes during
Hex
operation
Unit of
1
Default setting
setting
Register 014F
Changes during
Hex
operation
Unit of
1 %
Default setting
setting
Chapter 5
Yes
100
Yes
0
No
0.10
No
0
No
0
No
10
5-15