Basic Operation
H Setting the Motor Phase to neutral Resistance (n107)
·Set this parameter to 1/2 of the phase-to-phase resistance of the motor, or phase to
neutral resistance.
·Contact the manufacturer of the motor for the above resistance.
·This parameter is used as a vector control constant. Be sure to set the parameter cor-
rectly.
Motor Phase to neutral
n107
Resistance
Setting
0.000 to 65.50 (W)
range
Note 1. The value will be set in 0.001-W increments if the resistance is less than 10 W
and 0.01-W increments if the resistance is 10 W or over.
Note 2. The default setting for this parameter is the standard phase to neutral resist-
ance of the maximum applicable motor.
H Setting the Motor No-load Current (n110)
·Set the motor no-load current in percentage based on the rated current of the Inverter
as 100%.
·Contact the manufacturer of the motor for the motor no-load current.
·This parameter is used as a vector control constant. Be sure to set the parameter cor-
rectly. This set value is used for slip compensation as well.
Motor No-load Current
n110
Setting
0 to 99 (%)
range
Note The default setting for this parameter is the standard no-load current of the maxi-
mum applicable motor.
5-6
Register 016B
Hex
Unit of
See
setting
note 1
Register 016E
Changes during
Hex
operation
Unit of
1%
Default setting
setting
Chapter 5
Changes during
operation
Default setting
No
See note
No
See
note 2