Omron SYSDRIVE 3G3MV User Manual page 219

Multi-function compact inverter sysdrive 3g3mv series
Hide thumbs Also See for SYSDRIVE 3G3MV:
Table of Contents

Advertisement

Communications
D RUN Command (Register 0001 Hex)
Bit No.
0
1
2
3
4
5
6
7
8
9
10
11 to 15
Note There is an OR relationship between input from the control terminals and input
through communications. Therefore, if multi-function inputs of this register are
set to forward/stop and reverse/stop, it is possible to execute the RUN command
through the multi-function inputs. These settings are not, however, recom-
mended because these settings establish two command lines.
D Inverter Output (Register 0009 Hex)
Bit No.
0
1
2
3 to 15
Note The settings will be enabled if multi-function outputs 1 through 3 in n057 through
n059 are set to 18 for communications output. Then the corresponding output ter-
minal will be turned ON and OFF through communications.
H Broadcast Message with Slave Address: 00 (00 Hex)
Register No.
(Hex)
0000
Not used
0001
RUN command
0002
Frequency reference
0003 to 000F
Not used
Note 1. Data can be written to registers 0001 and 0002 only.
RUN command (1: RUN)
Forward/Reverse (1: Reverse)
External fault (External fault EF0)
Fault reset (1: Fault reset)
Multi-function input 1 (1: ON)
Multi-function input 2 (1: ON)
Multi-function input 3 (1: ON)
Multi-function input 4 (1: ON)
Multi-function input 5 (1: ON)
Multi-function input 6 (1: ON)
Multi-function input 7 (1: ON)
Not used
Multi-function contact output (1: ON)
Multi-function output 1 (1: ON)
Multi-function output 2 (1: ON)
Not used
Function
Function
Function
Description
---
Refer to the table below.
Set the frequency reference based on the
maximum frequency as 30,000.
---
Chapter 7
Write
7-25