Preparing for Operation and Monitoring
If a set range error results, the corresponding parameter number will flash. In
the case of a verification error, "oPj" (j is a figure) will flash.
Note 2. The following parameter set values or output frequency on hold cannot be
copied.
n176: Parameter copy function selection
n177: Parameter read-prohibit selection
Note 3. The following parameter set values cannot be copied if the Inverters are differ-
ent to each other in capacity.
n011 to n017: V/f setting
n036: Rated motor current
n080: Carrier frequency
n105: Torque compensation core loss
n106: Rated motor slip
n107: Motor wire-to-wire resistance
Note 4. Functions for 5.5/7.5kW Inverters cannot be copied to Inverters with different
capacities.
H Verifying the Parameter Set Values (vFy)
·In order to verify that the copied parameter set values in the Inverter coincide with
those in the EEPROM of the Digital Operator, set n176 for parameter copy function
selection to vFy.
Note The parameter set values can be verified provided that they are copied between
the Inverters that are the same in power supply specification and control mode
(i.e., V/f or vector control).
D Procedure to Verify the Parameter Set Values
Key
Indicator
sequence
3-16
n178: Error log
n179: Software version
n108: Motor leakage inductance
n109: Torque compensation limit
n110: Motor no-load current
n140: Energy-saving control coefficient K2
n158: Motor code
Display
example
Power ON
Press the Mode Key repeatedly until the
PRGM indicator is lit.
Use the Increment or Decrement Key to
display "n176."
Press the Enter Key. Then "rdy" will be
displayed.
Use the Increment Key to display "vFy."
Press the Enter Key so that the parameter
set values are verified, during which the
display flashes.
Chapter 3