Test Run
6. Setting Parameters
Set the parameters required for a test run.
S Perform the test run in V/f control mode. The control mode needs to be set to V/f
control since it will not be initialized. Set the rated motor current in order to prevent
the motor from burning due to overloading.
7. No-load Operation
Start the no-load motor using the Digital Operator.
S Set the frequency reference using the Digital Operator and start the motor using
key sequences.
8. Actual Load Operation
Connect the mechanical system and operate using the Digital Operator.
S When there are no difficulties using the no-load operation, connect the mechanical
system to the motor and operate using the Digital Operator.
9. Operation
Basic Operation:
Operation based on the basic settings required to start and stop the Inverter. Refer to
page 5-1.
Advanced Operation:
Operation that uses PID control or other functions. Refer to page 6-1.
S For operation within standard parameters, refer to Chapter 5 Basic Operation.
S Refer to Chapter 5 Basic Operation and Chapter 6 Advanced Operation for the vari-
ous advanced functions, such as energy-saving control, PID control, stall preven-
tion, carrier frequency setting, overtorque detection, torque compensation, and slip
compensation.
Chapter 4
4-5