Advanced Operation
Overtorque Detection
n097
Function Selection 2
Setting
0, 1
range
Set Values
Value
0
Detects overtorque from output torque.
1
Detects overtorque from output current.
·Set n097 to the item used for overtorque detection.
·In V/f control mode, overtorque is detected through the output current of the Inverter
regardless of the set value.
Overtorque Detection Level
n098
Setting
30 to 200 (%)
range
Set Values
·Set n098 to the type of overtorque detection level.
To detect the level through the output torque, set the torque in percentage based on
the rated motor torque as 100%.
To detect the level through the output current, set the current in percentage based on
the rated current of the Inverter as 100%.
Overtorque Detection Time
n099
Setting
0.1 to 10.0 (s)
range
Set Values
·Set the overtorque detection time.
·The Inverter will detect overtorque when the current (or torque) the same as or higher
than the detection level is output for the preset detection time.
6-36
Register 0161
Hex
Unit of
1
setting
Description
Register 0162
Hex
Unit of
1%
setting
Register 0163
Hex
Unit of
0.1 s
setting
Chapter 6
Changes during
No
operation
Default setting
0
Changes during
No
operation
Default setting
160
Changes during
No
operation
Default setting
0.1