Basic Operation
Pulse Train Frequency
n074
Reference Gain
Setting
--255 to 255
range
Pulse Train Frequency
n075
Reference Bias
Setting
--100 to 100
range
Frequency
reference (Hz)
H Pulse Train Frequency Reference Input Filter Constant (n076)
This parameter can be used to set a primary-delay digital filter for pulse train frequency
·
reference input.
This parameter setting is effective for smooth operation of the Inverter if the pulse train
·
input signal changes too rapidly or the signal is interfered with by noise.
The larger the set value is, the lower the response will be.
·
Pulse Train Frequency
n076
Reference Input Filter
Constant
Setting
0.00 to 2.00
range
5-26
n011: Maximum frequency
Register 014A
Hex
Unit of
1%
setting
Register 014B
Hex
Unit of
1%
setting
Register 014C
Hex
Unit of
0.01 s
setting
Chapter 5
Changes during
operation
Default setting
Changes during
operation
Default setting
Pulse train input frequency (Hz)
Changes during
operation
Default setting
Yes
100
Yes
0
No
0.10