Main Circuit Terminals - Omron SYSDRIVE 3G3MV User Manual

Multi-function compact inverter sysdrive 3g3mv series
Hide thumbs Also See for SYSDRIVE 3G3MV:
Table of Contents

Advertisement

Design
H Main Circuit Terminals
Symbol
Power supply input
R/L1
terminals
terminals
S/L2
T/L3
U/T1
Motor output
terminals
terminals
V/T2
W/T3
B1
Braking Resistor
connection terminals a Braking Resistor Unit. (Connect to detect overvoltage
connection terminals
B2
Connection terminals
+1
+1 and +2:
DC reactor
DC reactor
+2
connection terminals
+1 and --:
+1 and --:
--
DC power supply
input terminals
Ground terminal
Note 1. Connect single-phase input to both the R/L1 terminal and the S/L2 terminal.
Note 2. The maximum voltage at the output side corresponds to the power supply volt-
age for Inverter input.
2-14
Name
3G3MV-A2j: 3-phase 200 to 230 VAC
3G3MV-ABj: Single-phase 200 to 240 VAC (see note
3G3MV-ABj: Single-phase 200 to 240 VAC (see note
1)
1)
3G3MV-A4j: 3-phase 380 to 460 VAC
3-phase power supply output for driving motors. (see
note 2)
note 2)
3G3MV-A2j and 3G3MV-ABj: 3-phase 200 to
230 VAC
230 VAC
3G3MV-A4j: 3-phase 380 to 460 VAC
Terminals for attaching an external Braking Resistor or
a Braking Resistor Unit. (Connect to detect overvoltage
during braking.)
Connect the DC reactor for suppressing harmonics to
terminals +1 and +2.
When driving the Inverter with DC power, input the DC
When driving the Inverter with DC power, input the DC
power to terminals +1 and --.
(Terminal +1 is a positive terminal.)
(Terminal +1 is a positive terminal.)
Be sure to ground the terminal under the following
conditions.
3G3MV-A2j: Ground at a resistance of 100 W or less.
3G3MV-ABj: Ground at a resistance of 100 W or less.
3G3MV-A4j: Ground at a resistance of 10 W or less.
To conform to EC Directives, connect to the neutral
point of the power supply.
Note Be sure to connect the ground terminal directly
Description
to the motor frame ground.
Chapter 2