Omron SYSDRIVE 3G3MV User Manual page 58

Multi-function compact inverter sysdrive 3g3mv series
Hide thumbs Also See for SYSDRIVE 3G3MV:
Table of Contents

Advertisement

Design
Reactor Effects
Harmonics are effectively suppressed when the DC reactor is used with the AC reactor
as shown in the following table.
Harmonics
Harmonics
suppression
suppression
method
har-
monic
No reactor
65
AC reactor
38
DC reactor
30
DC and AC
28
reactors
H Connecting the Braking Resistor and Braking Resistor Unit
When running a load with a large inertia or a vertical axis, regeneration energy will return
to the Inverter. If OV (overvoltage) is generated during deceleration, this indicates that
the regeneration energy is exceeding the capacity of the Inverter. In this case, use a
Braking Resistor or a Braking Resistor Unit.
·Connect the Braking Resistor as shown in the following diagram.
Note 1. When using a Braking Resistor, install a thermal relay to monitor the tempera-
ture of the resistor.
Note 2. When using a Braking Resistor or a Braking Resistor Unit, be sure to include a
sequence whereby the power supply for the Inverter will be turned OFF in the
case of abnormal overheating. Not doing so may result in burning.
S Braking Resistor: Use the output of the thermal relay used to monitor the tempera-
ture of the thermometer.
S Braking Resistor Unit: Use the error contact output of the Braking Resistor Unit.
Harmonic generation rate (%)
5th
7th
11th
har-
har-
monic
monic
41
8.5
14.5
7.4
13
8.4
9.1
7.2
13th
17th
har-
har-
monic
monic
7.7
4.3
3.1
3.4
3.2
1.9
5
4.7
3.2
4.1
3.2
2.4
Chapter 2
19th
23rd
har-
har-
monic
monic
monic
2.6
1.8
1.7
1.3
3.0
2.2
1.6
1.4
25th
har-
2-35