Advanced Operation
Torque Compensation Limit
n109
Setting
0 to 250 (%)
range
Note 1. The Inverter in torque compensation control limits the torque at a current 1.5
times larger than the set value.
Note 2. This parameter is enabled only when the Inverter is in vector control.
H Adjusting the Torque and Response through the V/f Pattern
(n011 through n017)
·The Inverter in vector control uses the V/f pattern as the reference value of the output
voltage. Therefore, by adjusting the V/f pattern the output torque and response are
adjusted.
·If the application requires high torque, adjust the V/f pattern so that the output voltage
at the required frequency will be high. Furthermore, energy-saving effects can be
expected by decreasing the output voltage values in the frequency ranges where high
torque is not required.
Maximum Frequency
n011
(FMAX)
Setting
50.0 to 400.0 (Hz)
range
Maximum Voltage (VMAX)
n012
Setting
0.1 to 255.0 (0.1 to 510.0) (V)
range
n013
Maximum Voltage
Frequency (FA)
Setting
0.2 to 400.0 (Hz)
range
Middle Output Frequency
n014
(FB)
Setting
0.1 to 399.9 (Hz)
range
Middle Output Frequency
n015
Voltage (VC)
Setting
0.1 to 255.0 (0.1 to 510.0) (V)
range
6-4
Register 016D
Hex
Unit of
1%
setting
Register 010B
Hex
Unit of
0.1 Hz
setting
Register 010C
Hex
Unit of
0.1 V
setting
Register 010D
Hex
Unit of
0.1 Hz
setting
Register 010E
Hex
Unit of
0.1 Hz
setting
Register 010F
Hex
Unit of
0.1 V
setting
Chapter 6
Changes during
No
operation
Default setting
150
Changes during
No
operation
Default setting
60.0
Changes during
No
operation
Default setting
200.0
(400.0)
Changes during
No
operation
Default setting
60.0
Changes during
No
operation
Default setting
1.5
Changes during
No
operation
Default setting
11.0
(22.0)