Omron SYSDRIVE 3G3MV User Manual page 315

Multi-function compact inverter sysdrive 3g3mv series
Hide thumbs Also See for SYSDRIVE 3G3MV:
Table of Contents

Advertisement

List of Parameters
Param-
Regis-
Name
eter
ter No.
No.
n010
010A
Operation
selection at
Digital Opera-
tor interrup-
tion
n011
010B
Maximum fre-
quency
(FMAX)
n012
010C
Maximum
voltage
(VMAX)
n013
010D
Maximum
voltage fre-
quency (FA)
n014
010E
Middle output
frequency
(FB)
n015
010F
Middle output
frequency
voltage (VC)
n016
0110
Minimum out-
put frequency
(FMIN)
n017
0111
Minimum out-
put frequency
voltage
(VMIN)
n018
0112
Acceleration/
Deceleration
time setting
(n018)
Note 1. The values in brackets are those for 400-V-class Inverters.
Note 2. The values in brackets are those for 400-V-class Inverters.
Description
Select whether or not to detect the
OPR error (Digital Operator connec-
tion error).
0: No (The Inverter continues operat-
ing.)
1: Yes
(Error output turns ON and the
Inverter coasts to a stop)
Used to set the V/f pattern as the
basic characteristic of the Inverter.
V/f control mode: set output voltage
per frequency
Vector control mode: set for torque
adjustment
Output
voltage
n012
n015
n015
n017
n016
n016
n014
n014
n013
n013
Note Set the parameters so that the
following condition will be satis-
following condition will be satis-
fied.
n016
n014 < n013
Note The value set in n015 will be
Note The value set in n015 will be
ignored if parameters n016 and
ignored if parameters n016 and
n014 have the same value.
Select the acceleration or decelera-
tion time of the Inverter.
0: 0.1 s
(Less than 1,000 s: 0.1-s incre-
ments; 1,000 s or over: 1-s incre-
ments)
1: 0.01 s
(Less than 100 s: 0.01-s incre-
ments; 100 s or over: 0.1-s incre-
ments)
Set-
Unit
ting
of
range
set-
ting
0, 1
1
50.0 to
0.1
400.0
Hz
0.1 to
0.1 V
255.0
(0.1 to
510.0)
0.2 to
0.1
400.0
Hz
Fre-
quency
quency
n011
n011
(Hz)
(Hz)
0.1 to
0.1
399.9
Hz
0.1 to
0.1 V
255.0
n011
(0.1 to
510.0)
0.1 to
0.1
10.0
Hz
0.1 to
0.1 V
50.0
(0.1 to
100.0)
0, 1
1
Chapter 10
Default
Changes
Ref-
setting
during
er-
opera-
ence
tion
page
0
No
6-41
60.0
No
5-7
200.0
No
5-7
(400.0)
(see
note 1)
60.0
No
5-7
1.5
No
5-7
12.0
No
5-7
(24.0)
(see
note 2)
1.5
No
5-7
12.0
No
5-7
(24.0)
(see
note 2)
0
No
5-27
10-5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents