Preparing for Operation and Monitoring
H Sequence of Display
Note The following display is an example of the capacity displayed.
Voltage class
3-2-2 Parameter Copying Procedure
·To copy parameter values to another Inverter, take the following steps.
1. Set n001 for parameter write-prohibit selection/parameter initialization to 4.
2. Set n177 for parameter read-prohibit selection to 1 so that the parameters can be
read.
3. Read the parameter set value with the EEPROM of the Digital Operator with the item
rED selected.
4. Turn OFF the Inverter and remove the Digital Operator.
5. Mount the Digital Operator to the Inverter to which the parameters are to be copied.
Then turn ON the Inverter.
6. Copy the data in the EEPROM to the Inverter with the item CPy selected.
7. Check that the data is written correctly with the item vFy selected.
2: 3-phase 200 V
b: Single-phase 200 V
4: Three-phase 400 V
Reading
Writing
Verifying
Inverter
capacity
Software
version
Max. applicable motor capacity
0.1: 0.1 kW
0.2: 0.25 kW/0.37 kW
0.4: 0.55 kW
0.7: 1.1 kW
1.5: 1.5 kW
2.2: 2.2 kW
3.0: 3.0 kW
4.0: 4.0 kW
5.5: 5.5 kW
7.5: 7.5kW