Advanced Operation

6-10 Other Functions

The following description provides information on the other functions and
parameter settings of the Inverter.
Refer to Section 7 Communications for parameters used for communica-
tions.

6-10-1 Digital Operator Disconnection Error Detection

·This parameter setting is to select whether or not to detect Digital Operator connection
errors.
Operation Selection at
n010
Digital Operator Interruption
Setting
0, 1
range
Set Values
Value
0
The Digital Operator connection error is not detected (Nonfatal error)
1
The Digital Operator connection error is detected (Error output and the
Inverter coasts to a stop)

6-10-2 Motor Protection Functions (n037 and n038)

·This parameter setting is for motor overload detection (OL1).
Motor Protection
n037
Characteristics
Setting
0 to 2
range
Set Values
Value
0
Protection characteristics for general-purpose induction motors
1
Protection characteristics for Inverter-dedicated motors
2
No protection
·This parameter is used to set the electric thermal characteristics of the motor to be con-
nected.
·Set the parameter according to the motor.
·If a single Inverter is connected to more than one motor, set the parameter to 2 for no
protection. The parameter is also disabled by setting n036 for rated motor current to
0.0. However, this is not recommended.
Register 010A
Hex
Unit of
1
setting
Description
Register 0125
Hex
Unit of
1
setting
Description
Chapter 6
Changes during
No
operation
Default setting
0
Changes during
No
operation
Default setting
0
6-41