Maintenance Operations
Chapter 8
Malfunction Due to Unwanted Current Path
H
Inverter inputs may remain ON due to an unwanted current path for the controller out-
puts. With the wiring shown in the following table, if the controller output power supply is
less than 24 V DC or if the power is OFF, the current indicated by the arrow will flow and
the Inverter inputs will operate. If that occurs, insert a diode as shown in the diagram at
point A.
A
Control device
Inverter (control input)
S1 to 7
8-28