Preparing for Operation and Monitoring
·The above procedure is possible provided that the Inverters have the same power sup-
ply specification and control mode (i.e., V/f or vector control). It is not possible to copy
parameters from a 200-V model to a 400-V model or from an Inverter that is in V/f con-
trol mode to another that is in vector control mode, for example.
Note 1. The following parameter set values or output frequency on hold cannot be
copied.
n176: Parameter copy function selection
n177: Parameter read-prohibit selection
n178: Error log
n179: Software version
Note 2. The following parameter set values cannot be copied if the Inverters are differ-
ent to each other in capacity.
n011 to n017: V/f setting
n036: Rated motor current
n080: Carrier frequency
n105: Torque compensation core loss
n106: Rated motor slip
n107: Motor wire-to-wire resistance
n108: Motor leakage inductance
n109: Torque compensation limit
n110: Motor no-load current
n140: Energy-saving control coefficient K2
n158: Motor code
Note 3. Functions for 5.5/7.5kW Inverters cannot be copied to Inverters with different
capacities.
3-12
Chapter 3