Preparing for Operation and Monitoring
3-2-3 Parameter Read-prohibit Selection (Prohibiting
Data Written to the EEPROM of the Digital
Operator)
·To store the parameter set values in the EEPROM of the Digital Operator, set n177 for
parameter read-prohibit selection to 0. A protection error (PrE) will be detected by
attempting to read the parameter set values in the Inverter with rEd set. This protects
the parameter set values in the EEPROM from change. The PrE display is turned OFF
by pressing the Mode Key.
Parame-
Register
ter
n177
01B1
Note 1. No data can be written to n177 unless the default setting is changed. To write
data to this parameter, set n001 for parameter write-prohibit selection/parame-
ter initialization to 4.
Note 2. The parameter setting has an effect on the Digital Operator. If the Digital Opera-
tor with the data in the EEPROM protected is mounted to another Inverter, n117
will be set to 0 regardless of the n117 setting in the Inverter.
D Steps to Set Parameter Read-prohibit
Key
Indicator
sequence
3-18
Name
Description
Parame-
Used to keep the data in the
ter read-
EEPROM of the Digital
prohibit
Operator on hold.
selection
0: Parameter read-prohibit
(No data can be written to
the EEPROM)
1: Parameter read possible
(Data can be written to the
EEPROM)
Display
example
Setting
range
0, 1
Explanation
Power ON
Press the Mode Key repeatedly until the
PRGM indicator is lit.
Use the Increment or Decrement Key to
display "n177."
Press the Enter Key. The present set data will
be displayed.
Chapter 3
Unit of
Default
setting
setting
ges dur-
1
1
No
Chan-
ing
opera-
tion