Advanced Operation
·Set the width in percentage based on the power to be detected as 100%.
·Normally, the default setting does not need to be changed.
·The Inverter will operate with a power detection width of 10% if the value is set to 0.
Power Detection Filter
n162
Constant
Setting
0 to 255
range
Set Values
·Set this parameter to the filter time constant of the power detection block of the Inverter
operating in probe operation.
Filter time constant (ms) = Set value in n162 x 4 (ms)
·Normally, the default setting does not need to be changed.
·The Inverter will operate with a time constant of 20 ms if the value is set to 0.
6-12
Register 01A2
Hex
Unit of
1 (4 ms)
setting
Chapter 6
Changes during
No
operation
Default setting
5