Wiring Control Circuit Terminals - Omron SYSDRIVE 3G3MV User Manual

Multi-function compact inverter sysdrive 3g3mv series
Hide thumbs Also See for SYSDRIVE 3G3MV:
Table of Contents

Advertisement

Design

2-2-4 Wiring Control Circuit Terminals

A control signal line must be 50 m maximum and separated from power
lines.
The frequency reference must be input into the Inverter through shielded,
twisted-pair wires.
H Wiring Control I/O Terminals
Wire each control I/O terminal under the following conditions.
D Wires and Tightening Torque
Multi-function Contact Output (MA, MB, and MC)
Terminal
Tightening
screw size
torque N S m
M3
0.5 to 0.6
Sequential Input (S1 through S7 and SC), Multi-function Photocoupler
Output (P1, P2, PC), RS-422/485 Communications (R+, R- -, S+, S- -) and
Multi-function Analog Output (AM or AC), and Pulse Train Input (RP)
Terminal
Tightening
screw size
torque N S m
M2
0.22 to 0.25
Frequency Reference Input (FR, FS, and FC)
Terminal
Tighten-
screw size
ing torque
N S m
M2
0.22 to
0.25
0.25
2-38
Wire
Single wire
Stranded
wire
Wire
Single wire
Stranded
wire
Wire
Wire size
mm
(AWG)
Single wire 0.5 to 1.25
(20 to 16)
Stranded
0.5 to 0.75
wire
(20 to 18)
Wire size
Recom-
2
mm
(AWG)
mended
wire size
mm
0.5 to 1.25
0.75 (18)
(20 to 16)
0.5 to 1.25
(20 to 16)
Wire size
Recom-
2
mm
(AWG)
mended
wire size
mm
0.75 (18)
0.5 to 1.25
(20 to 16)
0.5 to 0.75
(20 to 18)
Recom-
2
mended
wire size
2
mm
(AWG)
0.75 (18)
Chapter 2
Cable
2
(AWG)
Cable with
polyethylene
polyethylene
sheath
sheath
Cable
2
(AWG)
Cable with
polyethylene
polyethylene
sheath
sheath
Cable
Special cable with
polyethylene sheath
polyethylene sheath
and shield for
and shield for
measurement use