Test Run

4
Setting the Motor Current Parameter
·Run the Inverter in V/f control mode for trial operation. The control mode is not initial-
ized. Therefore, set n002 to 0 for V/f control. Set the motor current parameter in n036 in
order to prevent the motor from burning due to overloading.
H Control Mode Setting
Parame-
Register
ter
n002
0102
Key sequence
In approximately
1 s.
4-8
Name
Description
Control
Sets the control mode for the
mode
Inverter.
selection
0: V/f control mode
1: Vector control mode
Note
1. The control mode
is not initialized
with n001 set-
tings.
Note
2. There are param-
eters that are
changed accord-
ing to the set
value in n002. For
details, refer to
5-1-2 Setting the
Control Mode
(n002).
Indicator
Display
example
Setting
range
0, 1
Explanation
The parameter number is displayed.
Use the Increment or Decrement Key to
display "n002."
Press the Enter Key to display the set value in
n002.
Use the Increment or Decrement key to set
n002 to 0 unless the value is already set to 0,
during which the display flashes.
Press the Enter Key so that the set value will
be entered and the data display will be lit.
The parameter number will be displayed again
in approximately 1 s.
Chapter 4
Unit of
Default
setting
setting
ges dur-
1
0
No
Chan-
ing
opera-
tion