Error code
(Hexadecimal)
1C14H
1C15H
1C1BH
1C1CH
1C21H
1C40H
1C41H
1C42H
1C43H
1C44H
1C45H
1C46H
Downloaded from
ManualsNet.com
Error name
Error details and causes
Home position return speed
The setting value of the home position return basic
error
parameter "[Pr.46] Home position return speed"
exceeds "[Pr.8] Speed limit value".
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Home position return speed
The setting value of the home position return basic
error
parameter "[Pr.46] Home position return speed" is
smaller than "[Pr.7] Bias speed at start".
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Home position return
The setting value of the home position return detailed
acceleration time selection
parameter "[Pr.51] Home position return acceleration
error
time selection" is outside the setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Home position return
The setting value of the home position return detailed
deceleration time selection
parameter "[Pr.52] Home position return deceleration
error
time selection" is outside the setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Home position return torque
The setting value of the home position return detailed
limit value error
parameter "[Pr.55] Operation setting for incompletion
of home position return" is outside the setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Network parameter error
[Add-on baseSystem "Ver. 1.15" or earlier]
(total number of stations <
The station number of the slave station to connect to
station number)
network in "Network Configuration Settings" exceeds
the total number of slave stations configured.
[Operation status at error occurrence]
The target station cannot be connected to the drive
unit.
WDT error
A WDT error of the driver was detected.
[Operation status at error occurrence]
The system stops immediately.
Unsupported driver
An unsupported driver was connected.
connection
[Operation status at error occurrence]
Instance creation of the driver fails.
SLMP communication error
An error occurred in SLMP communication.
[Operation status at error occurrence]
During communication initialization
• Communication with the driver is not possible.
Network parameter error
The station numbers of the slave stations to connect to
(station No. order error)
the network are not listed in ascending order in
"Network Configuration Settings".
[Operation status at error occurrence]
The target station cannot be connected to the drive
unit.
SLMP communication error
Response timeout was detected in SLMP
(timeout)
communication.
[Operation status at error occurrence]
SLMP communication is not established.
Time synchronization error
There is a station that has disconnected due to
incomplete time synchronization.
[Operation status at error occurrence]
The target station cannot be connected to the drive
unit.
search engine
Remedy
After the setting value is set to equal to or less
than "[Pr.8] Speed limit value", turn the PLC
READY signal [Y0] from OFF to ON.
After the setting value is set to equal to or more
than "[Pr.7] Bias speed at start", turn the PLC
READY signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Set the station number of the slave station to be
connected to the network to be less than or
equal to the total number of slave stations.
• When a stop error of the CPU module is
detected, check the details of the CPU
module error and take actions.
• Review the communication cycle.
• Check for abnormalities in the surrounding
environment, such as noise, and remove the
cause.
• After taking the above measures, switch the
power on again or reset the CPU module.
Connect a supported driver.
• Review the slave object setting.
• Check the manual of the driver.
Set the station numbers of the slave stations to
connect to the network in ascending order.
Review the transient transmission time. It is
obtained by the following equation.
(Transient transmission time = Communication
period interval setting - Cyclic transmission time
- System reservation time)
• Shorten the communication cycle.
• Check for abnormalities in the surrounding
environment, such as noise, and remove the
cause.
• Connect only to the stations for which the
network configuration has been set.
14 TROUBLESHOOTING
14.5 List of Error Codes