Error code
(Hexadecimal)
1BC3H
1BC4H
1BC5H
1BC6H
1BCBH
1BCCH
Downloaded from
ManualsNet.com
Error name
Error details and causes
Stop group 3 rapid stop
The setting value of the detailed parameter 2 "[Pr.39]
selection error
Stop group 3 rapid stop selection" is outside the setting
range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/rapid stop) of the detailed parameter
2 Rapid stop selection (stop group 3). (Note that the
deceleration stop only occurs during the manual pulse
generator operation.)
Outside allowance circular
The setting value of the detailed parameter 2 "[Pr.41]
interpolation error width
Allowable circular interpolation error width" is outside
the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/rapid stop) of the detailed parameter
2 Rapid stop selection (stop group 3). (Note that the
deceleration stop only occurs during the manual pulse
generator operation.)
External command function
The setting value of the detailed parameter 2 "[Pr.42]
selection error
External command function selection" is outside the
setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/rapid stop) of the detailed parameter
2 Rapid stop selection (stop group 3). (Note that the
deceleration stop only occurs during the manual pulse
generator operation.)
Manual pulse generator
The setting value of the detailed parameter 2 "[Pr.122]
speed limit mode error
Manual pulse generator speed limit mode" is outside
the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/rapid stop) of the detailed parameter
2 Rapid stop selection (stop group 3). (Note that the
deceleration stop only occurs during the manual pulse
generator operation.)
Input signal logic selection
The setting values of the detailed parameter 1 "[Pr.22]
setting error
Input signal logic selection" are different in the axis that
uses the same input signal.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Restart allowable range error
The setting value of the detailed parameter 2 "[Pr.84]
Restart allowable range when servo OFF to ON" is
outside the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/rapid stop) of the detailed parameter
2 Rapid stop selection (stop group 3). (Note that the
deceleration stop only occurs during the manual pulse
generator operation.)
search engine
Remedy
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
With the setting of the axis is matched, turn the
PLC READY signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
14 TROUBLESHOOTING
14.5 List of Error Codes