Error code
(Hexadecimal)
1BBEH
1BBFH
1BC0H
1BC1H
1BC2H
14 TROUBLESHOOTING
640
14.5 List of Error Codes
Downloaded from
ManualsNet.com
Error name
Error details and causes
Acceleration/deceleration
The setting value of the detailed parameter 2 "[Pr.34]
process selection setting
Acceleration/deceleration process selection" is outside
error
the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/rapid stop) of the detailed parameter
2 Rapid stop selection (stop group 3). (Note that the
deceleration stop only occurs during the manual pulse
generator operation.)
S-curve ratio setting error
The setting value of the detailed parameter 2 "[Pr.35]
S-curve ratio" is outside the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/rapid stop) of the detailed parameter
2 Rapid stop selection (stop group 3). (Note that the
deceleration stop only occurs during the manual pulse
generator operation.)
Illegal rapid stop deceleration
The setting value of the detailed parameter 2 "[Pr.36]
time
Rapid stop deceleration time" is outside the setting
range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/rapid stop) of the detailed parameter
2 Rapid stop selection (stop group 3). (Note that the
deceleration stop only occurs during the manual pulse
generator operation.)
Stop group 1 rapid stop
The setting value of the detailed parameter 2 "[Pr.37]
selection error
Stop group 1 rapid stop selection" is outside the setting
range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/rapid stop) of the detailed parameter
2 Rapid stop selection (stop group 3). (Note that the
deceleration stop only occurs during the manual pulse
generator operation.)
Stop group 2 rapid stop
The setting value of the detailed parameter 2 "[Pr.38]
selection error
Stop group 2 rapid stop selection" is outside the setting
range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/rapid stop) of the detailed parameter
2 Rapid stop selection (stop group 3). (Note that the
deceleration stop only occurs during the manual pulse
generator operation.)
search engine
Remedy
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.