• Turn OFF "[Cd.183] Execution prohibition flag" after "2: Completed" is set to "[Md.503] Pre-reading data analysis status".
• Because each positioning module operates independently after the start, the following operation is performed.
- Even if a module stops due to an error, other modules where no error occurs continue to operate.
- Even if stop signals are input at the same time in the program, the stop signal detection timing may not be the same and the stop positions may be different.
• When the inter-module synchronization is enabled, "[Cd.183] Execution prohibition flag" is read in the processing caused
by the interruption of the inter-module synchronous interruption (I44). Therefore, if "[Cd.183] Execution prohibition flag" is
operated without using the inter-module synchronous interruption (I44), it is not read. If the inter-module synchronous
interruption (I44) is used, the processing is performed even when "[Cd.183] Execution prohibition flag" is not used in the
event, but the inter-module synchronous start cannot be guaranteed.