Chapter 2
Room Requirements for the TX9000 and TX9200 Systems
Cabling and Room Considerations for Second Row Seating For the TX9200
THESE MEASUREMENTS DEPEND ON THE PLACEMENT OF THE REFLECTOR WALL.
Caution
Failure to account for the reflector wall depth can result in an incorrect trench location. For
systems that use a wall-mounted reflector wall, add 3" (76 mm) to the rear wall dimensions to account
for the thickness of the reflector wall and mount. For free-standing systems that use the minimum
distance between the reflector wall and the wall of the room, add 8" (203 mm). Add more depth if you
plan to install the reflector wall farther away from the rear wall.
Figure 2-5
Cable Trench Location for TX9200
Cisco TelePresence System TX9000 and TX9200 Assembly, Use & Care, and Field-Replaceable Unit Guide
2-15