3.2 Cabinets

3.2.1 Transformer Cabinet

For the technical specifications of a transformer cabinet provided by the customer,
see the instructions provided by the manufacturer.
Capacity
Voltage Ratio
2.5 MVA
10 kV/0.4 kV
2.0 MVA
10 kV/0.4 kV
1.6 MVA
10 kV/0.4 kV
1.25 MVA
10 kV/0.4 kV

3.2.2 Cable Inlet and Bus Tie Cabinet (Separate or Combined)

Table 3-1 Cable inlet switches and bus tie switches in separate cabinets
Switch
Specifications
5000 A/4P E6
5000 A/3P E6
4000 A/4P E6
4000 A/3P E6
4000 A/4P E4
4000 A/3P E4
3200 A/4P E4
3200 A/3P E4
Issue 03 (2023-02-08)
NO TICE
Thermal
Insulation
Class
F
F
F
F
Breaking
Cabinet Weight
Capacity
I
= I
= 100 kA
≤ 1100 kg
cu
cs
I
= I
= 100 kA
≤ 850 kg
cu
cs
I
= I
= 100 kA
≤ 1000 kg
cu
cs
I
= I
= 100 kA
≤ 780 kg
cu
cs
I
= I
= 66 kA
≤ 760 kg
cu
cs
I
= I
= 66 kA
≤ 730 kg
cu
cs
I
= I
= 66 kA
≤ 680 kg
cu
cs
I
= I
= 66 kA
≤ 650 kg
cu
cs
Copyright © Huawei Digital Power Technologies Co., Ltd.
Cabinet
Cabinet Dimensions (H x W x
Weight
D)
≤ 5870 kg
2000 mm x 2200 mm x 1500
mm
≤ 4260 kg
2000 mm x 2200 mm x 1500
mm
≤ 3850 kg
2000 mm x 2200 mm x 1500
mm
≤ 3100 kg
2000 mm x 2000 mm x 1500
mm
Cabinet Dimensions (H x W x D)
2000 mm x 1200 mm x 1000 mm
2000 mm x 1000 mm x 1000 mm
2000 mm x 1200 mm x 1000 mm
2000 mm x 1000 mm x 1000 mm
2000 mm x 800 mm x 1000 mm
2000 mm x 800 mm x 1000 mm
2000 mm x 800 mm x 1000 mm
2000 mm x 800 mm x 1000 mm