Huawei FusionPower6000 3.0 User Manual page 146

Table of Contents

Advertisement

FusionPower6000 3.0
User Manual (Not Against a Wall)
Figure 4-65 Cable connections to the ECC800-Pro and smart ETH gateway
Step 8 Connect the electronic lock cables to the transformer cabinet.
Port on the
Temperature
Controller Terminal
Block
3, 4
5, 6
Issue 03 (2023-02-08)
NO TE
● Place smart ETH gateway 1 in the cable inlet and bus tie cabinet or the cable inlet
cabinet, smart ETH gateway 2 in the IT maintenance bypass cabinet, and smart ETH
gateway 3 in the IT feeder cabinet 3 or maintenance bypass and feeder cabinet for
mechanical load.
● The WAN1 ports of the cable inlet and bus tie cabinet, cable inlet cabinet, bus tie
cabinet, maintenance bypass cabinet, and feeder cabinet are located on the centralized
monitoring module. The FE port of the UPS is located on the control module.
Definition
Travel switch NC
contact
Travel switch NO
contact
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Screw
Connects to the
M2.5
trip signal of the
medium-voltage
PDU.
Connects to the
M2.5
interlock signal
of the medium-
voltage PDU.
4 Installation and Cable Connection
Torque
0.4–0.6 N·m
0.4–0.6 N·m
139