Feeder Cabinet - Huawei FusionPower6000 3.0 User Manual

Table of Contents

Advertisement

FusionPower6000 3.0
User Manual (Not Against a Wall)
Maintenance
Bypass Switch
Specifications
for IT Load
I
: rated ultimate short-circuit breaking capacity; I
cu
capacity
Table 3-7 IT maintenance bypass switches and emergency switches (optional) in combined cabinets
Maintenance
Bypass Switch
Specifications
for IT Load
4000 A/3P E2
3200 A/3P E2
2500 A/3P E2
2000 A/3P E2
1600 A/3P E1
I
: rated ultimate short-circuit breaking capacity; I
cu
capacity

3.2.6 Feeder Cabinet

MCCB Specifications and
Maximum Switch
Quantity
630 A, 7 PCS
400 A, 7 PCS
250 A/160 A/100 A/63 A, 9
PCS
Issue 03 (2023-02-08)
Maintenance
Breaking
Bypass Switch
Capacity
Specifications
for Mechanical
Load
Emergency
Breaking
Switch
Capacity
Specifications
4000 A/3P E2
I
kA
3200 A/3P E2
I
kA
2500 A/3P E2
I
kA
2000 A/3P E2
I
kA
1250 A/3P E1
I
kA
Maximum Capacity
of Vertical Copper
Bars
2500 A
2500 A
2000 A
Copyright © Huawei Digital Power Technologies Co., Ltd.
Cabinet
Weight
: rated operating short-circuit breaking
cs
Cabinet
Weight
= I
= 66
≤ 940 kg
cu
cs
= I
= 66
≤ 700 kg
cu
cs
= I
= 66
≤ 730 kg
cu
cs
= I
= 66
≤ 620 kg
cu
cs
= I
= 66
≤ 420 kg
cu
cs
: rated operating short-circuit breaking
cs
Cabinet
Weight
≤ 510 kg
≤ 480 kg
≤ 410 kg
3 Technical Specifications
Cabinet Dimensions (H x W
x D)
Cabinet Dimensions (H x W
x D)
2000 mm x 800 mm x 1000
mm
2000 mm x 800 mm x 1000
mm
2000 mm x 800 mm x 1000
mm
2000 mm x 800 mm x 1000
mm
2000 mm x 600 mm x 1000
mm
Cabinet Dimensions (H x W
x D)
2000 mm x 600 mm x 1000
mm
2000 mm x 600 mm x 1000
mm
2000 mm x 600 mm x 1000
mm
79