Huawei FusionPower6000 3.0 User Manual page 147

Table of Contents

Advertisement

FusionPower6000 3.0
User Manual (Not Against a Wall)
Port on the
Temperature
Controller Terminal
Block
7, 9
Step 9 (Optional) Connect cables to the temperature controller in the transformer
cabinet.
Port on the
Temperature
Controller Terminal
Block
11, 12
13, 14
15, 16
17, 18
51, 52
Do not connect an external power supply.
Step 10 (Fire control linkage scenario) Connect fire control signal cables to the feeder
cabinet.
Port on the XT Terminal Block
(Definition)
1 (QF1 24V+), 2 (QF1 GND)
Issue 03 (2023-02-08)
Definition
Electronic lock
power supply
(220 V AC or 110
V DC)
Definition
NO contact of
the fan remote
signal output
NO contact of
the
overtemperature
alarm signal
output
NO contact of
the
overtemperature
tripping signal
output
NO contact of
the fault alarm
signal output
Internal buzzer
signal
Description
Fire control shunt signal
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Screw
Connects to the
M2.5
DC panel of the
medium-voltage
PDU.
Description
Screw
Optional signal
M2.5
Optional signal
M2.5
Optional signal
M2.5
Optional signal
M2.5
Connects to the
M2.5
travel switch NO
contact.
Screw
M2.5
4 Installation and Cable Connection
Torque
0.4–0.6 N·m
Torque
0.4–0.6 N·m
0.4–0.6 N·m
0.4–0.6 N·m
0.4–0.6 N·m
0.4–0.6 N·m
Torque
0.4–0.6 N·m
140

Advertisement

Table of Contents
loading

Table of Contents