User Manual (Not Against a Wall)

2.4.4 UPS

The UPS stabilizes the voltage of the utility power. When the utility power fails,
the UPS automatically switches the power supply to battery strings to ensure the
normal operation of loads. The cabinet width is 800 mm.
IT UPSs or groups of IT UPSs can be connected in parallel.
A maximum of two UPSs for mechanical loads can be connected in parallel.
Figure 2-23 Appearance
(A) Front door closed
(2) Cable hole
(5) Mains input switch
(8) Switch handle
(11) Bypass module
Issue 03 (2023-02-08)
A maximum of four UPSs can be connected in parallel.
Two groups of UPSs (3+2) or (2+2) can be connected in parallel.
NO TE
● The figure uses the 600 kVA model as an example. The number of power modules varies
depending on the configuration. Four power modules are configured for the 400 kVA
model, five power modules for the 500 kVA model, and six power modules for the 600
kVA model.
● Switches share one switch handle. Take out the handle when you operate switches and
reinstall it after the operations are complete.
Copyright © Huawei Digital Power Technologies Co., Ltd.
(B) Front door open
(3) Output switch
(6) Monitoring display unit
(MDU)
(9) Control module
(12) Power modules
2 Product Overview
(1) Top outlet kit (optional)
(4) Bypass input switch
(7) SPDs
(10) Intelligent detection card
45