Table 3-4 Battery electrical specifications
Item
Battery type
Battery voltage
(lead-acid battery)
Battery cold start
Charger output
power
Battery string
sharing
Charging voltage
(lead-acid battery)
The UPS supports the SmartLi. For details about the parameters, see the
User Manual .
Issue 03 (2023-02-08)
Specifications
● Lead-acid battery (VRLA)
● SmartLi: SmartLi 2.0 and SmartLi 3.0 are supported.
360–600 V DC
● 12 V batteries (30–50 batteries optional, 0 by default)
– 40–50 batteries: not derated
– 38–39 batteries: derated to 90%
– 34–37 batteries: derated to 80%
– 30–33 batteries: derated to 70%
● 2 V batteries (180–300 batteries optional, 0 by default)
– 240–300 batteries: not derated
– 228–239 batteries: derated to 90%
– 204–227 batteries: derated to 80%
– 180–203 batteries: derated to 70%
NOTE
The number of batteries is 0 by default and needs to be set based on site
requirements. Batteries have no neutral wire, and an odd number of batteries are
supported.
If a utility power outage occurs, batteries can start the UPS to supply
power to loads.
The maximum charge power is 15% of power of a single module, and the
charge current is limited to 30 A.
● Lead-acid battery: Battery string sharing is supported in a parallel
system. No battery is shared by default.
● SmartLi 2.0: Battery string sharing is supported in a parallel system. No
battery is shared by default.
● SmartLi 3.0: Battery string sharing is not supported.
● Equalized charging voltage: 2.35 V/cell
● Float charging voltage: 2.25 V/cell
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Technical Specifications
SmartLi
77