Figure 4-72 Installing a PAD
(1) Adjusting screws
Before removing the PAD from the support, remove the power cable to avoid
dragging the cable.
----End

4.12 Verifying the Installation

No.
1
2
3
Issue 03 (2023-02-08)
NO TICE
Check Item
FusionPower6000
installation
Equipment
appearance
Cabinet doors
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
Acceptance Criteria
● The installation conforms to the design
requirements.
● The equipment should be installed in a dry
area. Do not install it under areas prone to
water leakage, such as air conditioner vents,
ventilation vents, feeder windows of the
equipment room, or water pipes. Ensure
that no liquid enters the equipment to
prevent faults or short circuits.
● The equipment is intact and free from
inclination, distortion, paint flake-off, and
rust.
● All connections are secure.
● The cabinet doors are secured and in
position.
● The doors of adjacent cabinets do not block
each other.