Huawei FusionPower6000 3.0 User Manual page 99

Table of Contents

Advertisement

FusionPower6000 3.0
User Manual (Not Against a Wall)
Cable
MCCB output
power cable
(L1/L2/L3/N)
MCCB output
cable (PE)
Equipotential
ground cable for
a cabinet
Internal signal
cable of the
FusionPower6000
Issue 03 (2023-02-08)
Recommended Size
● 630 A: 2 x 185 mm
● 630 A: 2 x 150 mm
● 400 A: 2 x 95 mm
2
● 250 A: 95 mm
2
● 160 A: 50 mm
2
● 100 A: 25 mm
2
● 63 A: 25 mm
2
● 630 A: 150 mm
2
● 400 A: 95 mm
2
● 250 A: 50 mm
2
● 160 A: 25 mm
2
● 100 A: 25 mm
2
● 63 A: 25 mm
2
16 mm
-
Copyright © Huawei Digital Power Technologies Co., Ltd.
Recommended
Type
600 V/1000 V Cat
2
5 conductor
2
2
600 V/1000 V Cat
5 conductor
600 V/1000 V Cat
5 conductor
-
4 Installation and Cable Connection
Description
Connects to the load power
input. Crimp a DT terminal
to the cable.
2
● 185 mm
: M12 DT
terminal
2
● 150 mm
: M12 DT
terminal
2
● 95 mm
: M12 DT
terminal
2
● 50 mm
: M10 DT
terminal
2
● 25 mm
: M10 DT
terminal
Prepare the cable and
terminal by yourself.
Connects to the load PE.
Crimp a DT terminal to the
cable.
2
● 150 mm
: M12 DT
terminal
2
● 95 mm
: M12 DT
terminal
2
● 50 mm
: M10 DT
terminal
2
● 25 mm
: M10 DT
terminal
Prepare the cable and
terminal by yourself.
Connects to the
equipotential ground point
of the equipment room.
Crimp an OT terminal to
the cable.
● Transformer cabinet: M8
OT terminal
● Other cabinets: M6 OT
terminal
Prepare the cable and
terminal by yourself.
Delivered with cabinets.
92