Huawei FusionPower6000 3.0 User Manual page 148

Table of Contents

Advertisement

FusionPower6000 3.0
User Manual (Not Against a Wall)
Port on the XT Terminal Block
(Definition)
3 (QF1 COM), 4 (QF1 NO)
5 (QF2 24V+), 6 (QF2 GND)
7 (QF2 COM), 8 (QF2 NO)
9 (QF3 24V+), 10 (QF3 GND)
11 (QF3 COM), 12 (QF3 NO)
13 (QF4 24V+), 14 (QF4 GND)
15 (QF4 COM), 16 (QF4 NO)
17 (QF5 24V+), 18 (QF5 GND)
19 (QF5 COM), 20 (QF5 NO)
21 (QF6 24V+), 22 (QF6 GND)
23 (QF6 COM), 24 (QF6 NO)
25 (QF7 24V+), 26 (QF7 GND)
27 (QF7 COM), 28 (QF7 NO)
29 (QF8 24V+), 30 (QF8 GND)
31 (QF8 COM), 32 (QF8 NO)
A feeder cabinet with eight MCCB output modules is used as an example.
Step 11 (2N scenario) Connect the ATS secondary circuit cables.
Port in Route A
Cable Inlet and
Bus Tie
Cabinet/Bus Tie
Cabinet
QF3 XT4-18
QF3 XT4-19
QF3 XT4-20
Issue 03 (2023-02-08)
Description
Fire control shunt feedback
signal
Fire control shunt signal
Fire control shunt feedback
signal
Fire control shunt signal
Fire control shunt feedback
signal
Fire control shunt signal
Fire control shunt feedback
signal
Fire control shunt signal
Fire control shunt feedback
signal
Fire control shunt signal
Fire control shunt feedback
signal
Fire control shunt signal
Fire control shunt feedback
signal
Fire control shunt signal
Fire control shunt feedback
signal
Port in Route B
Definition
Cable Inlet
Cabinet
QF2 XT4-1
QF2 ATS power supply
QF2 XT4-2
QF2 ATS power supply
QF2 XT4-3
QF2 ATS power supply
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
Screw
Torque
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
Screw
Torque
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
M2.5
0.4–0.6 N·m
141