Huawei FusionPower6000 3.0 User Manual page 98

Table of Contents

Advertisement

FusionPower6000 3.0
User Manual (Not Against a Wall)
Cable
(Lead-acid
battery scenario)
Battery cable for
the 600 kVA UPS
(Lead-acid
battery scenario)
Battery cable for
the 500 kVA UPS
(Lead-acid
battery scenario)
Battery cable for
the 400 kVA UPS
(Lithium battery
scenario) UPS
battery cable
Issue 03 (2023-02-08)
Recommended Size
● Positive: 4 x 185 mm
● Negative: 4 x 185 mm
2
● PE: 240 mm
● Positive: 3 x 185 mm
● Negative: 3 x 185 mm
2
● PE: 240 mm
● Positive: 2 x 240 mm
● Negative: 2 x 240 mm
2
● PE: 240 mm
For details, see
IEC-60364-5-52 and
SmartLi User Manual .
Copyright © Huawei Digital Power Technologies Co., Ltd.
Recommended
Type
600 V/1000 V Cat
2
5 conductor
2
600 V/1000 V Cat
2
5 conductor
2
600 V/1000 V Cat
2
5 conductor
2
-
4 Installation and Cable Connection
Description
Connects to a battery
string. Crimp an M16 DT
terminal to the cable.
Prepare the cable and
terminal by yourself.
One DT terminal can be
crimped on each of the two
sides of the copper bar.
That is, two DT terminals
can be crimped at one bolt.
Connects to a battery
string. Crimp an M16 DT
terminal to the cable.
Prepare the cable and
terminal by yourself.
One DT terminal can be
crimped on each of the two
sides of the copper bar.
That is, two DT terminals
can be crimped at one bolt.
Connects to a battery
string. Crimp an M16 DT
terminal to the cable.
Prepare the cable and
terminal by yourself.
One DT terminal can be
crimped on each of the two
sides of the copper bar.
That is, two DT terminals
can be crimped at one bolt.
Connects to a battery
string.
Prepare the cable and
terminal by yourself.
One DT terminal can be
crimped on each of the two
sides of the copper bar.
That is, two DT terminals
can be crimped at one bolt.
91