Huawei FusionPower6000 3.0 User Manual page 70

Table of Contents

Advertisement

FusionPower6000 3.0
User Manual (Not Against a Wall)
Indicators and Buttons
Table 2-8 Indicators on the ECC800-Pro main control module
Indicator
RUN
ALM
RF_Z
Issue 03 (2023-02-08)
Color
Green
Red
Green
Copyright © Huawei Digital Power Technologies Co., Ltd.
Name
Status
Running
Steady on
status
indicator
Off
Blinking
at long
intervals
Blinking
at short
intervals
Alarm
Steady on
indicator
Off
Communicati
Blinking
on status
at long
indicator
intervals
Blinking
at super
short
intervals
2 Product Overview
Description
The power supply is
normal and the program
is being loaded.
The power supply is
abnormal.
The software runs
properly and the
management system is
successfully registered
(the indicator blinks at 0.5
Hz, on for 1s and then off
for 1s).
The ECC800-Pro does not
register with the
management system (the
indicator blinks at 5 Hz,
on for 0.1s and then off
for 0.1s).
A system failure alarm is
generated.
The system is normal.
A network is set up, and
no node access is allowed
(the indicator blinks at 0.5
Hz, on for 1s and then off
for 1s).
A network is set up, and
node access is allowed
(the indicator blinks at 10
Hz, on for 0.05s and then
off for 0.05s).
63