No.
8
9
10
Issue 03 (2023-02-08)
Check Item
Foreign matter is
cleaned up from the
cabinets and
enclosure frames.
Signs
Copper bars on the
cabinet top
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
Acceptance Criteria
● There is no foreign matter (such as copper
wires and screws) on the top of the cabinets
or enclosure frames.
● There is no foreign matter on copper bars.
● There is no foreign matter around the
switch terminals.
● There is no foreign matter on the bottom
plates of the cabinets.
● There is no foreign matter on the rear
module subracks.
● The interior of the cabinets and enclosure
frames is clean and free from dust,
excessive cable ties, cable residues, screws,
washers, nuts, and other sundries.
● The desiccant (if any) inside the cabinets
has been removed before power-on.
● The air filters of the cabinets are intact.
● All signs are correct, clear, and complete.
Warning signs are placed at prominent
positions of the FusionPower6000, no-
stepping signs are placed on the epoxy
boards on the top, no-tilting signs are
placed on cabinets, and cables are labeled.
● The labels of the switches, SPDs, and
secondary circuit components match the
electrical diagrams.
● Copper bars on the cabinet top are not
deformed.
● The heat shrink tubing on copper bars is
intact, free from damage and cracks.
● The specifications of the bolts at the joints
of copper bars are correct. The bolts are
tightened to the specified torque. The
fastening positions are clearly marked.
● The copper bar temperature sensors are
intact, with the cables and probes properly
connected.
● The copper bar current transformers (CT)
are installed in the correct direction. The
side marked P1 faces the cable inlet.
● The cabinet top is clean and free from
foreign matter.
150